| Plan Review Notes For Permit 01071195 |
| Permit Number |
01071195 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-08 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY METHOD OF GROUND- | | | ING FOR TRANSFORMER PER 250-30. | | | | | | 2)NOTE: PLEASE NOTE THAT PANEL "MLA" IS | | | SHOWN W/OUT MAIN. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS WERE SHOWN | | | FOR PANELS BUT NEEDED FOR MAIN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|