| Plan Review Notes For Permit 01071119 |
| Permit Number |
01071119 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-11-14 00:00:00 | BUILDING PLAN REVIEW | | | 700 S ROSEMARY # 204 | | | PLAN REVIEW " 01071119 | | | ARCH: CRAIG MOSSEY | | | TEL: (561) 416-9059 | | | FAX: (561) 416-9058 | | | BOCA RATON, FL 33486 | | | SBC=1997 STANDARD BUILDING CODE | | | SBC* AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- SBC 903.5 (1) FIRE SPRINKLER PLANS | | | ARE REQUIRED FOR TYPE II CONSTRUCTION, | | | TOBE SUBMITTED AS PART OF THE BUIULDING | | | PERMIT PACKAGE. A SEPERATE PERMIT PLANS | | | AND FEES SHALL BE REQUIRED. | | | | | | 2)-NORTH WALL FIXED SEATING AT RAMP # 3 | | | SHALL BE A MINIMUM OF 3'-8", A REDDUC- | | | TION OF 1'-0" FOR THE FIXED SEATING | | | AGAINST THE NORTH WALL,(SEE SBC1019.10.3 | | | .3) THE EGRESS ISLE THEN HAS 2'-8". | | | | | | 3)- SHEET A2.0 WEST TENANT SEPERATION | | | WALL IS INDICATED AS A 1 HR.WALL, SBC | | | 704.1 ASSEMBLY REQUIRES A 2 HR SEPERA- | | | TION. |
|