| Plan Review Notes For Permit 01071119 |
| Permit Number |
01071119 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-07 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY WHERE THE LOAD | | | CALCULATIONS ARE SHOWN AND WHERE THE | | | CONTINUOUS LOADS AT 125%.EVERYTHING IS | | | SHOWN AT CONNECTED LOAD. | | | 2)NOTE: PLEASE SHOW WHERE LOADS CALCS | | | ARE SHOWN FOR TRACK LIGHTING PER 220-12B | | | | | | 3)NOTE: PLEASE NOTE THAT THE ELECTRICAL | | | PLANS SHOW TRANSFORMER AND ASSC EQUIP- | | | -MENT ABOVE WALK-IN COOLER, BUT ARCH | | | DETAILS ON A3.0 SHOW A DIFFERENT LOCAT- | | | -ION? PLEASE SUBMIT A DETAIL ON THE | | | OPEN MOUNTING/PLATFORM FOR TRANSFORMER. | | | PLEASE NOTE THAT ALL MUST MEET 110-26 | | | AND 450-13 ECT | | | | | | 4)NOTE: PLEASE NOTE THAT NOTE ON PLANS | | | MENTION GC TO SUBMIT DETAILS FOR THE | | | TRANSFORMER PLATFORM/MOUNTING ETC. | | | THIS IS REQ`D TO BE SUBMITTED FOR | | | PLAN REVIEW.PLEASE SUBMIT BOTH ELECTRICA | | | L AND STRUCTURAL DETAILS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|