| 2001-09-17 00:00:00 | BUILDING PLAN REVIEW |
| | 700 S ROSEMARY AVE |
| | PERMIT # 01071119 |
| | "NV LONGE" |
| | ARCHITECT: CRAIG MOSSEY |
| | TEL: (561) 416-9059 |
| | FAX: (561) 416-9058 |
| | BOCA RATON, FL 33486 |
| | SBC= 1997 STANDARD BUILDING CODE |
| | FL ACC CODE= 1997 FLORIDA ACCESSIBILITY |
| | CODE |
| | |
| | 1)_ FROM PREVIOUS REVIEW: SBC 1204.2 |
| | RESTROOMS SHALL HAVE NONABSORBANT FLOORS |
| | AND WALLS TO A HEIGTH OF 4'-0". |
| | |
| | 2)- FROM PREVIOUS REVIEW: FL ACC CODE |
| | 4.5.1. FLOOR SURFACES ALONG ACCESSIBILE |
| | ROUTES AND IN ACCESSIBLE ROOMS AND |
| | SPACESINCLUDING FLOORS, WALKS,STAIRS |
| | CURBS AND RAMPS SHALL BE FIRM, STABLE |
| | AND SLIP RESISTANT. A STATIC COEFFICIENT |
| | OF FRICTION OF 0.6 IS RECOMMENDED FOR |
| | FLOORS AND 0.8 FOR RAMPS. |
| | |
| | 3)- DOORS E-1, E-2 PROVIDE PRODUCT INFOR |
| | MATION FOR 2 HR. FIRE RATING FOR DOORS |
| | AND THE TRANSOMS ABOVE.WINDOWS 1-4 AL- |
| | SO WILL REQUIRE 2 HR. FIRE RATING. DOOR |
| | X-1 INDICATES FLUSH SHOW DETAIL FOR 1HR |
| | RATING AND THE HARDWARE FOR THE DOOR, |
| | SBC 1012.1.2 (1-3). |
| | |
| | 4)- FROM PRREVIOUS REVIEW ; ADDITIONAL |
| | INFORMATION REQUIRED, SHEET A7.1 DETAIL |
| | #4, 3" MEDIUM DENSE FOAM, FLAME & SMOKE |
| | DEVELOPMENT. |
| | |
| | 5)- REVOLVING DOORS SBC 1012.3(1-6) |
| | ENTRANCE DOORS AT LOUNGE #2 ARE TO COM- |
| | PLY. THERE IS ALAO A DISCREPANCY FROM |
| | SHEET A.2 AND AC.1, P1 & E.1. THE SUB |
| | TRADE SHEETS SHOW A AWING DOOR WHWEREAS |
| | A.2 DOESN'T? |
| | |
| | 6)- FROM PREVIOUS REVIEW, SBC 403.2.4. |
| | PLATFORM CONSTRUCTION, FOR RAISED PLAT- |
| | FORMS & RAMPS. FLOORS ARE TO BE BUILT AS |
| | A TYPE II BUILDING CONSTRUCTION. LIVE |
| | LOADS AS PER CHAPTER 16. 100 LBS/ SQ FT. |
| | TABLE 600 TYPE II CON. FLOORS (2HR. RAT- |
| | ING) NONCOMBUSTIBLE 604,609.2.1, |
| | FLOOR FINISH 803.7.1, SEE SBC SEC 706, |
| | 707. |
| | AC-1 INDICATES A/C DUCTS BENEATH PLAT- |
| | FORM, E.2 (D) INDICATES THAT THERE ARE |
| | TO BE RECESSED LIGHTS IN FLOORING PLEASE |
| | DETAIL. |
| | |
| | 7)- DISCREPANCY, AREA 21 DANCE AREA VIP |
| | 2'-4" ELEVATION VS. DETAIL 6/A9.2. |
| | |
| | 8)- SBC 903.5 (1) FIRE SPRINKLER PLANS |
| | ARE REQUIRED FOR TYPE II CONSTRUCTION. |
| | |
| | 9)- SHEET A.9.1 SEC 8 2X4 BLOCKING. |
| | SBC 609.2.1 NONCOMBUSTIBLE MATERIALS |
| | FRAMING & BACKING IN WALLS, FIRE RESIS- |
| | TANT TREATED WOOD MAY BE USED. |
| | |
| | 10)- FROM PREVIOUS REVIEW, SHEET A9.3 |
| | HANGING CEILING DETAILS, EXPANSION BOLTS |
| | INTO EXISTING SLAB? TYPE OF ANCHOR?DEPTH |
| | OF ANCHOR? |
| | |
| | 11)- LETTER FROM ENGINEER FOR THE ADDITI |
| | ONAL LOADING OF BAR JOIST, THAT THE BAR |
| | JOIST WILL TAKE THE ADDITIONAL LOADING. |
| | AC.2 ROOF CURB DETAILS : NOTE #4 SEE |
| | STRUCTURAL DETAILS, THERE ARE NONE? |
| | THE ADDITIONAL LOADS FOR THE AIR HAND- |
| | LERS DOESN,T INDICATE IF THE LOADS ARE |
| | BEING TRANSFERED TO THE TOP OR BOTTOM |
| | CORD OF THE BAR JOIST, PLEASE HAVE THE |
| | ENGINEER OF RECORD INDICATE? |
| | |
| | 12)- A9.3 SECTION #2 FINISH INFORMATION |
| | ON THE SUSPENDED DOME. SMOKE DEVELOPMENT |
| | AND FLAME SPREAD. |
| | |
| | 13)- ROOF /CEILING ASSEMBLY: TABLE 600 |
| | 1 HR PROTECTED FOR TYPE II STRUCTURE |
| | (BAR JOIST) SHOW COMPLIANCE. |
| | |
| | 14)- A1.0 NORTH WALL FIXED SEATING AT |
| | RAMP # 3 3'-8" REQUIRED, MINIMUM. |
| | SBC 1019.10.3.3 SUBTRACT 12" FOR THE |
| | FIXED SEATING AGAINST THE NORTH WALL. |
| | ACCESS ISLE NOW ONLY HAS 2'-8" NOT LEGAL |
| | |
| | |
| | 15)- A 1.0 AT THE FOOT OF RAMP #1 AND AT |
| | THE END OF RAMP #2 "HATCHED MARKS" |
| | INDICATING WHAT? |