| 2001-09-12 00:00:00 | DENIED |
| | REFERENCE SPC-94 - FACBC-97 |
| | 1) COMMENT #1 FROM PLAN REVIEW 8-30 NOT |
| | ADDRESSED. PLANS TO BE ROUTED TO THE |
| | PALM BEACH COUNTY HEALTH UNIT, DIVISION |
| | OF ENVIRONMENTAL HEALTH, (901 EVERNIA ST |
| | WPB FLA 33401), (561) 355-3018 FOR PLAN |
| | REVIEW BEFORE CITY OF WPB PLAN REVIEW. |
| | 2) PAGE A4.1 FINISH SCHEDULE, PLEASE SUB |
| | MIT MANUFACTURE INFORMATION ON THE PRO- |
| | DUCT USED TO KEEP WALLS AND FLOORS NON- |
| | ABSORBANT. (CARMINAR) |
| | 3) PAGES P.1, P.2 & P.4 FD-2 SHOULD READ |
| | FS-2 FOR FLOOR SINK. |
| | 4) PAGE P.2 WATER HAMMER ARRESTORS TO BE |
| | SIZED AND LOCATED PER MANUFACTURS INSTAL |
| | LATION INSTRUCTIONS AND WH-PDI 201. NOT |
| | ON TOP OF DROP AS SHOWN ON WATER RISER |
| | DIAGRAM. |
| | 5) PAGE P.2 WATER RISER DIAGRAM & WATER |
| | RISER NOTES, PAGE P.5 PLUMBING SPECIFIC- |
| | ATIONS #'S 7 & 8. AIR CHAMBERS SHALL |
| | COMPLY WITH SPC-94 SECT'S. 607.8.2 & |
| | 607.8.3 SHALL BE ACCESSABLE AND RECHARG- |
| | ABLE. |
| | 6) PAGE P.2 SANITARY RISER DIAGRAM. LAVS |
| | NOT VENTED PROPERLY. SHOW VENT THRU ROOF |
| | OR OTHER VENT DETAIL. |
| | 7) PAGE P.2 SANITARY RISER DIAGRAM. |
| | FUNNEL DRAINS NOT APPROVED, ALL INDIRECT |
| | WASTE TO DRAIN TO FLOOR SINKS. SPC 804.5 |
| | 8) PAGE P.3 WATER HEATER DETAIL. SHUT |
| | OFF VALVE ON SUPPLY SIDE (COLD) TO BE |
| | ACCESSABLE. PUT VALVE CLOSE TO HEATER. |
| | 9) PAGE P.5 PLUMBING SPECIFICATIONS. #5 |
| | HUB DRAINS NOT APPROVED. |
| | |
| | REVIEW BY KEN STEVENS |