Plan Review Notes
Plan Review Notes For Permit 01071119
Permit Number 01071119
Review Stop P
Sequence Number 2
Notes
Date Text
2001-09-12 00:00:00DENIED
 REFERENCE SPC-94 - FACBC-97
 1) COMMENT #1 FROM PLAN REVIEW 8-30 NOT
 ADDRESSED. PLANS TO BE ROUTED TO THE
 PALM BEACH COUNTY HEALTH UNIT, DIVISION
 OF ENVIRONMENTAL HEALTH, (901 EVERNIA ST
 WPB FLA 33401), (561) 355-3018 FOR PLAN
 REVIEW BEFORE CITY OF WPB PLAN REVIEW.
 2) PAGE A4.1 FINISH SCHEDULE, PLEASE SUB
 MIT MANUFACTURE INFORMATION ON THE PRO-
 DUCT USED TO KEEP WALLS AND FLOORS NON-
 ABSORBANT. (CARMINAR)
 3) PAGES P.1, P.2 & P.4 FD-2 SHOULD READ
 FS-2 FOR FLOOR SINK.
 4) PAGE P.2 WATER HAMMER ARRESTORS TO BE
 SIZED AND LOCATED PER MANUFACTURS INSTAL
 LATION INSTRUCTIONS AND WH-PDI 201. NOT
 ON TOP OF DROP AS SHOWN ON WATER RISER
 DIAGRAM.
 5) PAGE P.2 WATER RISER DIAGRAM & WATER
 RISER NOTES, PAGE P.5 PLUMBING SPECIFIC-
 ATIONS #'S 7 & 8. AIR CHAMBERS SHALL
 COMPLY WITH SPC-94 SECT'S. 607.8.2 &
 607.8.3 SHALL BE ACCESSABLE AND RECHARG-
 ABLE.
 6) PAGE P.2 SANITARY RISER DIAGRAM. LAVS
 NOT VENTED PROPERLY. SHOW VENT THRU ROOF
 OR OTHER VENT DETAIL.
 7) PAGE P.2 SANITARY RISER DIAGRAM.
 FUNNEL DRAINS NOT APPROVED, ALL INDIRECT
 WASTE TO DRAIN TO FLOOR SINKS. SPC 804.5
 8) PAGE P.3 WATER HEATER DETAIL. SHUT
 OFF VALVE ON SUPPLY SIDE (COLD) TO BE
 ACCESSABLE. PUT VALVE CLOSE TO HEATER.
 9) PAGE P.5 PLUMBING SPECIFICATIONS. #5
 HUB DRAINS NOT APPROVED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377