2001-09-21 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 2.PROVIDE PLAN INDICATING TERMINATION
 OF EXHAUST FANS.
  
 3.INDICATE MATERIAL AND R-VALUE OF
 DUCTWORK.
  
 4.CLARIFY VENTILATION FOR RESTROOMS.
 NO EXHAUST FANS ARE INDICATED ON
 PLAN.AIR SHALL NOT BE RECIRCULATED
 FROM THE RESTROOMS AS PER 1997 SMC
 503.3.1.
  
 5.DO NOT SEE EXHAUST FANS F-5 AND F-6
 LOCATION ON PLAN.
  
 6.ACCESS FOR AHU SHALL BE ADAQUATE FOR
 SERVICE AND REPLACEMENT OF THE
 LARGEST PIECE TO THE EQUIPMENT.
  
 7.AUXILIARY DRAIN PAN SHALL HAVE OVER-
 FLOW PROTECTION BY MEANS OF A FLOAT
 SWITCH OR A DRAIN LINE TERMINATING
 AT A CONSPICUOUS POINT TO SERVE AS
 AN ALARM THAT THE REGULAR DRAIN IS
 RESTRICTED.
  
 8.PROVIDE DETAIL OF THE CONDENSER TO
 WALK-IN COOLER.IF CONDENSER IS
 LOCATED ON THE ROOF, PROVIDE A
 DETAIL OF STAND AND HOW IT WILL BE
 ATTACHED TO THE ROOF.18" MINIMUM
 BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL.
  
 NOTE:ADDITIONAL PERMIT REQUIRED FOR
 WALK-IN COOLER.PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA
 WITH PERMIT APPLICATION.
  