| Date |
Text |
| 2001-09-21 00:00:00 | ******************DENIED**************** |
| | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW: |
| | |
| | 1.AIR BALANCE SCHEDULE SHOWING |
| | COMPLIANCE WITH 1997 SMC 501.2. |
| | |
| | 2.PROVIDE PLAN INDICATING TERMINATION |
| | OF EXHAUST FANS. |
| | |
| | 3.INDICATE MATERIAL AND R-VALUE OF |
| | DUCTWORK. |
| | |
| | 4.CLARIFY VENTILATION FOR RESTROOMS. |
| | NO EXHAUST FANS ARE INDICATED ON |
| | PLAN.AIR SHALL NOT BE RECIRCULATED |
| | FROM THE RESTROOMS AS PER 1997 SMC |
| | 503.3.1. |
| | |
| | 5.DO NOT SEE EXHAUST FANS F-5 AND F-6 |
| | LOCATION ON PLAN. |
| | |
| | 6.ACCESS FOR AHU SHALL BE ADAQUATE FOR |
| | SERVICE AND REPLACEMENT OF THE |
| | LARGEST PIECE TO THE EQUIPMENT. |
| | |
| | 7.AUXILIARY DRAIN PAN SHALL HAVE OVER- |
| | FLOW PROTECTION BY MEANS OF A FLOAT |
| | SWITCH OR A DRAIN LINE TERMINATING |
| | AT A CONSPICUOUS POINT TO SERVE AS |
| | AN ALARM THAT THE REGULAR DRAIN IS |
| | RESTRICTED. |
| | |
| | 8.PROVIDE DETAIL OF THE CONDENSER TO |
| | WALK-IN COOLER.IF CONDENSER IS |
| | LOCATED ON THE ROOF, PROVIDE A |
| | DETAIL OF STAND AND HOW IT WILL BE |
| | ATTACHED TO THE ROOF.18" MINIMUM |
| | BETWEEN THE ROOF SURFACE AND THE |
| | BOTTOM OF THE SUPPORT RAIL. |
| | |
| | NOTE:ADDITIONAL PERMIT REQUIRED FOR |
| | WALK-IN COOLER.PROVIDE PLANS |
| | AND MANUFACTURER SUBMITTAL DATA |
| | WITH PERMIT APPLICATION. |
| | |