Plan Review Notes
Plan Review Notes For Permit 01071119
Permit Number 01071119
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-08-14 00:00:001) PLATFORMS IF PERMANANT, ARE TO BE
 CONSTRUCTED OF MATERIALS FO THE TYPE
 OF CONSTRUCTION IN WHICH THE PLATFORMS
 ARE LOCATED.
 2) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 3) THE SHARED FOYER MUST BE AT LEAST
 7'- 6" HIGH. ANY PROJECTIONS FROM THE
 CEILING MUST BE AT LEAST 7'- 0 FROM THE
 FINISHED FLOOR.
 4) PLEASE PROVIDE PRODUCT APPROVALS FOR
 2 HOUR FIRE PROOF TEMPERED GLASS AND
 DOORS SHOWN ON THE DRAWINGS.
 5) NO ILLUMINATED EXIT SIGNS OR
 EMERGENCY LIGHTS SHOWN.
 6) NO FIRE ALARM EQUIPMENT SHOWN ON THE
 DRAWINGS.
 7) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910