| Plan Review Notes For Permit 01071119 |
| Permit Number |
01071119 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-08-14 00:00:00 | 1) PLATFORMS IF PERMANANT, ARE TO BE | | | CONSTRUCTED OF MATERIALS FO THE TYPE | | | OF CONSTRUCTION IN WHICH THE PLATFORMS | | | ARE LOCATED. | | | 2) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 3) THE SHARED FOYER MUST BE AT LEAST | | | 7'- 6" HIGH. ANY PROJECTIONS FROM THE | | | CEILING MUST BE AT LEAST 7'- 0 FROM THE | | | FINISHED FLOOR. | | | 4) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | 2 HOUR FIRE PROOF TEMPERED GLASS AND | | | DOORS SHOWN ON THE DRAWINGS. | | | 5) NO ILLUMINATED EXIT SIGNS OR | | | EMERGENCY LIGHTS SHOWN. | | | 6) NO FIRE ALARM EQUIPMENT SHOWN ON THE | | | DRAWINGS. | | | 7) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|