| Plan Review Notes For Permit 01071119 |
| Permit Number |
01071119 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-18 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT DETAIL ON GROUND- | | | -ING OF TRANSFORMER PER 250-30 | | | | | | 2)NOTE: PLEASE NOTE THAT TRANSFORMER | | | SHOWN ON E.1 AND E.4 ARE TWO DIFFERENT | | | SIZES, PLEASE CLARIFY. | | | PLEASE PROVIDE STRUCTUAL MOUNTING | | | DETAIL ON E.4 FOR TRANSFORMER. | | | PLEASEKEEP IN MIND 450-9 AND 450-13 | | | | | | 3)NOTE: PLEASE NOTE AS PER LOCAL AMEND- | | | -MENTS:210-50 OUTLET SPACING IS EVERY | | | 20' OF UNENCUMBERED WALL SPACE. | | | PLEASE REVISE OUTLET LAYOUT. | | | | | | 4)NOTE: PLEASE NOTE ALL TRACK LIGHTING | | | CALCULATIONS TO BE SHOWN PER 220-12B | | | | | | 5)NOTE: PLEASE NOTE, ALL CONTINUOUS | | | LOADS ARE TO BE SHOWN AT 125%. PLEASE | | | NOTE 230-42 AND 215-2/3. | | | | | | 6)NOTE: PLEASE NOTE EQUIPMENT(DISCONNECT | | | -S FOR TRANSFORMER DO NOT MEET DEDICATED | | | ELECTRICAL SPACE PER 110-26. FLOOR TO | | | CEILING. PLEASE NOTE THAT THE TOP OF | | | WALK-IN COOLERS ARE ALOMOST ALWAYS USED | | | FOR STORAGE. PLEASE FIND A DEDICATED | | | SPACE PER. 110-26 AND 384-7. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|