Plan Review Notes
Plan Review Notes For Permit 01071119
Permit Number 01071119
Review Stop E
Sequence Number 2
Notes
Date Text
2001-09-18 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT DETAIL ON GROUND-
 -ING OF TRANSFORMER PER 250-30
  
 2)NOTE: PLEASE NOTE THAT TRANSFORMER
 SHOWN ON E.1 AND E.4 ARE TWO DIFFERENT
 SIZES, PLEASE CLARIFY.
 PLEASE PROVIDE STRUCTUAL MOUNTING
 DETAIL ON E.4 FOR TRANSFORMER.
 PLEASEKEEP IN MIND 450-9 AND 450-13
  
 3)NOTE: PLEASE NOTE AS PER LOCAL AMEND-
 -MENTS:210-50 OUTLET SPACING IS EVERY
 20' OF UNENCUMBERED WALL SPACE.
 PLEASE REVISE OUTLET LAYOUT.
  
 4)NOTE: PLEASE NOTE ALL TRACK LIGHTING
 CALCULATIONS TO BE SHOWN PER 220-12B
  
 5)NOTE: PLEASE NOTE, ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%. PLEASE
 NOTE 230-42 AND 215-2/3.
  
 6)NOTE: PLEASE NOTE EQUIPMENT(DISCONNECT
 -S FOR TRANSFORMER DO NOT MEET DEDICATED
 ELECTRICAL SPACE PER 110-26. FLOOR TO
 CEILING. PLEASE NOTE THAT THE TOP OF
 WALK-IN COOLERS ARE ALOMOST ALWAYS USED
 FOR STORAGE. PLEASE FIND A DEDICATED
 SPACE PER. 110-26 AND 384-7.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372