| Plan Review Notes For Permit 01071077 |
| Permit Number |
01071077 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-01-08 00:00:00 | NOTE: | | | 1. SUB DUCT MUST BE MINIMUM OF 26 GA AND | | | RISERS WHICH ARE SUBJECT TO MOISTURE | | | SHALL BE LINED WITH SUITABLE MATERIAL | | | TO PREVENT DETERIORATION OF DRYWALL | | | ENCLOSURE PER LOCAL AMENDMENTS TO THE | | | SMC 610.1.3 | | | 2. DRYER DUCT SHAFT SHALL TERMINATE TO | | | THE OUTSIDE OF THE BUILDING WITH A FAN | | | RATED FOR THE SHAFT SIZE AND HAVE A | | | BACKDRAFT DAMPER AND NO BIRDSCREEN OR | | | EACH DRYER DUCT SHALL BE RUN SEPARATELY | | | TO PREVENT POSITIVE PRESSURE ON | | | NONRUNNING DRYERS APARTMENTS | | | 3. BATHROOM EXHAUST DUCT TO TERMINATE | | | OUTSIDE OF BUILDING TO REMOVE MOISTURE | | | LADEN AIR AND PREVENT INTRODUCTION OF | | | AIR FROM SHAFT INTO APTS. FAN TO BE | | | SIZED FOR SIZE OF SHAFT AND HAVE | | | BIRDSCREEN. | | | THIS APPLIES TO ALL MECHANICAL PERMITS | | | FOR PINNACLE PALMS PROJECT. | | | PROVIDE ENGINEER'S DESIGN SHOWING | | | COMPLIANCE WITH ABOVE |
|