Plan Review Notes
Plan Review Notes For Permit 01071052
Permit Number 01071052
Review Stop P
Sequence Number 2
Notes
Date Text
2001-09-10 00:00:00DENIED
  
 REFERENCE: SPC-94 - FACBC-97
  
 1) COMMENT #1 FROM PREVIOUS REVIEW NOT
 ADDRESSED. PLEASE COMPLY WITH RUNNING
 THE GREASE LINE SEPARATE FROM THE SANIT-
 ARY LINE. PAGE P-1
  
 2) PAGE P-1, WATER RISER DIAGRAM STILL
 SHOWS AIR CHAMBERS AT EACH FIXTURE.
 LOCATION OF WATER HAMMER ARRESTORS SHALL
 BE PER MANUFACTURE'S INSTALLATION IN-
 STRUCTIONS NOT AT TOP OF DROP AS SHOWN.
 PLEASE LOCATE ARRESTORS WHERE INSTRUCTED
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377