| Plan Review Notes For Permit 01071052 |
| Permit Number |
01071052 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-10 00:00:00 | DENIED | | | | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) COMMENT #1 FROM PREVIOUS REVIEW NOT | | | ADDRESSED. PLEASE COMPLY WITH RUNNING | | | THE GREASE LINE SEPARATE FROM THE SANIT- | | | ARY LINE. PAGE P-1 | | | | | | 2) PAGE P-1, WATER RISER DIAGRAM STILL | | | SHOWS AIR CHAMBERS AT EACH FIXTURE. | | | LOCATION OF WATER HAMMER ARRESTORS SHALL | | | BE PER MANUFACTURE'S INSTALLATION IN- | | | STRUCTIONS NOT AT TOP OF DROP AS SHOWN. | | | PLEASE LOCATE ARRESTORS WHERE INSTRUCTED | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|