Plan Review Notes
Plan Review Notes For Permit 01071052
Permit Number 01071052
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-14 00:00:00DENIED
  
 1) GREASE LINE REQUIRED TO PICK UP FLOOR
 DRAINS, FLOOR SINKS, HAND SINKS, AND
 THREE COMPARTMENT SINK. MINIMUN 750 GAL
 GREASE TRAP REQUIRED. PLEASE CONTACT
 RODNEY COMPO AT WEST PALM BEACH UTILITY
 (561) 837-4074
  
 2) AIR CHAMBERS TO MEET SPC-94 REQUIRE-
 MENTS 607.8.2 & 607.8.3 - MUST BE RE-
 CHARGEABLE AND ACCESSABLE.
  
 3) PERMINATE SHIPS LADDER REQUIRED FOR
 WATER HEATER TO MAKE IT ACCESSABLE AND
 SERVICEABLE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377