| Plan Review Notes For Permit 01071052 |
| Permit Number |
01071052 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-14 00:00:00 | DENIED | | | | | | 1) GREASE LINE REQUIRED TO PICK UP FLOOR | | | DRAINS, FLOOR SINKS, HAND SINKS, AND | | | THREE COMPARTMENT SINK. MINIMUN 750 GAL | | | GREASE TRAP REQUIRED. PLEASE CONTACT | | | RODNEY COMPO AT WEST PALM BEACH UTILITY | | | (561) 837-4074 | | | | | | 2) AIR CHAMBERS TO MEET SPC-94 REQUIRE- | | | MENTS 607.8.2 & 607.8.3 - MUST BE RE- | | | CHARGEABLE AND ACCESSABLE. | | | | | | 3) PERMINATE SHIPS LADDER REQUIRED FOR | | | WATER HEATER TO MAKE IT ACCESSABLE AND | | | SERVICEABLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|