| Plan Review Notes For Permit 01071052 |
| Permit Number |
01071052 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-09 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFOMRATION | | | FOR REVIEW. | | | | | | | | | 1.AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE | | | AS PER 1997 SMC 406.1 AND NFPA 90A | | | 4-4.4.3. | | | | | | 3.PLEASE INDICATE AS TO WHERE THE | | | CONDENSATE IS TO TERMINATE. | | | | | | NOTE, CONDENSATE WILL FOLLOW THE | | | PITCH OF THE ROOF SO LONG AS THE | | | PITCH IS DOWN. | | | | | | NOTE:ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPRESSION AND WALK | | | IN COOLER/FREEZER.PLEASE | | | SUBMIT PLANS AND MANUFACTURER | | | SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|