2001-08-09 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFOMRATION
 FOR REVIEW.
  
  
 1.AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE
 AS PER 1997 SMC 406.1 AND NFPA 90A
 4-4.4.3.
  
 3.PLEASE INDICATE AS TO WHERE THE
 CONDENSATE IS TO TERMINATE.
  
 NOTE, CONDENSATE WILL FOLLOW THE
 PITCH OF THE ROOF SO LONG AS THE
 PITCH IS DOWN.
  
 NOTE:ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPRESSION AND WALK
 IN COOLER/FREEZER.PLEASE
 SUBMIT PLANS AND MANUFACTURER
 SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  