Plan Review Notes
Plan Review Notes For Permit 01071037
Permit Number 01071037
Review Stop P
Sequence Number 1
Notes
Date Text
2001-07-30 00:00:00FAILED
 REFERENCE SPC-94 SGC-97
  
 1) PAGE M-1 PLUMBING NOTES.
 #11 AIR CHAMBERS TO BE INSTALLED IN
 ACCORDANCE WITH SPC-94 SECT. 607.8.2 &
 607.8.3. WATER HAMMER ARRESTORS TO BE
 INSTALLED IN ACCORDANCE TO MANUFACTURES
 INSTALLATION INSTRUCTIONS.
 #14 HOT WATER CIRCULATING SYSTEM TO
 BE INSULATED PER ENERGY CODE.
 #16 GAS TO BE PERMITTED SEPARATELY.
 SEE ATTACHED GAS PERMIT APPLICATION RE-
 QUIREMENTS SHEET. ALL INFORMATION ON
 THAT SHEET THAT IS APPLICABLE MUST BE
 RETURNED WITH GAS PERMIT APPLICATION.
  
 PAGE M-1 SANITARY RISER DIAGRAM.
 POWDER ROOM W/C IS NOT VENTED PROPERLY.
 BATH #3 BATHTUB IS NOT VENTED PROPERLY.
 RISER DIAGRAM TO REFLECT FLOOR PLAN, BAR
 SINK SHALL BE TAKEN OFF BUILDING DRAIN
 BEFORE CABANA BATH.
 W/M SHALL BE TAKEN OFF THE STACK LOWER
 THAN LAUNDRY SINK ON BOTH LAUNDRY STACKS
 DRIP HANG TRAP NOT VENTED PROPERLY.
 1/2 BATH AT WORKSHOP ON FAR SIDE OF
 GARAGE NOT SHOWN ON SANITARY RISER DIA-
 GRAM.
 BIDET NOT VENTED PROPERLY IN MASTER
 BATH.
  
 BACKFLOW REQUIRED ON WATER SERVICE IF
 A SWIMMING POOL IN INSTALLED.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377