| 2001-08-08 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2)NOTE: PLEASE NOTE THAN RISER DIAGRAM |
| | NEEDS TO HAVE ALL WIRE SIZES CLARIFIED. |
| | PLEASE NOTE THAT PLANS SHOW 6-3/0`S |
| | PARALLELED?? W/ #3`S. PLEASE NOTE DOWN |
| | SIZING OF NEUTRAL MORE THAN TWO SIZES |
| | REQUIRES SUBMITTAL OF NEUTRAL CALCS. |
| | PLEASE SHOW EACH RUN AS INDIVIDUAL. |
| | YOU SHOW 3/0`S TO 100A PANEL?? |
| | 2)NOTE;PLEASE NOTE THAT THERE IS NO |
| | EQUIGROUNDING CONDUCTOR SHOWN AFTER |
| | FIRST |
| | MEANS OF DISCONNECT TO ANY PANEL PER |
| | 250-122. |
| | |
| | 3)NOTE: PLEASE NOTE THAT PLANS SHOW |
| | PARALLEL 350 MCM`S. JUST NOTE THAT THIS |
| | SIZE WIRE WELL EXCEEDS WHAT IS REQ`D |
| | FORA 400A SERVICE. PLANS SHOW PARALLEL |
| | 250MCM FROM FPL HANDHOLE.? |
| | |
| | 4)NOTE: PLEASE NOTE THAT THE OUTLET |
| | SPACING ALONG KITCHEN COUNTERSPACE DOES |
| | NOT SEEM TO MEET 210-52-C-1 |
| | |
| | 5)NOTE: PLEASE NOTE THAT OUTLET ON BACK |
| | PORCH TO BE SHOWN AS GFI. 210-8 |
| | |
| | 6) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | THERE ARE SOME MISSING. |
| | |
| | 7) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 8) PLEASE NOTE EITHER MISSING EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210-70 OF THE NEC. |
| | MISSING IN TOWER. |
| | |
| | 9) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING OUTLET IN BEDROOM UPSTAIRS. |
| | |
| | 10)NOTE: PLEASE NOTE THAT "MDP" AND |
| | METER LOCATION NEEDS TO BE SHOWN ON |
| | PLANS. |
| | |
| | 11)NOTE: PLEASE NOTE THAT ALL PLANS |
| | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| | ING A TITLE BLOCK, MUST BE SIGNED, DATED |
| | AND SEALED BY THE ARCH/ENGINEER OF |
| | RECORD. PER FS/FAC 481.221 & 471.025 |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |