Plan Review Notes
Plan Review Notes For Permit 01071037
Permit Number 01071037
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE THAN RISER DIAGRAM
 NEEDS TO HAVE ALL WIRE SIZES CLARIFIED.
 PLEASE NOTE THAT PLANS SHOW 6-3/0`S
 PARALLELED?? W/ #3`S. PLEASE NOTE DOWN
 SIZING OF NEUTRAL MORE THAN TWO SIZES
 REQUIRES SUBMITTAL OF NEUTRAL CALCS.
 PLEASE SHOW EACH RUN AS INDIVIDUAL.
 YOU SHOW 3/0`S TO 100A PANEL??
 2)NOTE;PLEASE NOTE THAT THERE IS NO
 EQUIGROUNDING CONDUCTOR SHOWN AFTER
 FIRST
 MEANS OF DISCONNECT TO ANY PANEL PER
 250-122.
  
 3)NOTE: PLEASE NOTE THAT PLANS SHOW
 PARALLEL 350 MCM`S. JUST NOTE THAT THIS
 SIZE WIRE WELL EXCEEDS WHAT IS REQ`D
 FORA 400A SERVICE. PLANS SHOW PARALLEL
 250MCM FROM FPL HANDHOLE.?
  
 4)NOTE: PLEASE NOTE THAT THE OUTLET
 SPACING ALONG KITCHEN COUNTERSPACE DOES
 NOT SEEM TO MEET 210-52-C-1
  
 5)NOTE: PLEASE NOTE THAT OUTLET ON BACK
 PORCH TO BE SHOWN AS GFI. 210-8
  
 6) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 THERE ARE SOME MISSING.
  
 7) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 8) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 MISSING IN TOWER.
  
 9) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING OUTLET IN BEDROOM UPSTAIRS.
  
 10)NOTE: PLEASE NOTE THAT "MDP" AND
 METER LOCATION NEEDS TO BE SHOWN ON
 PLANS.
  
 11)NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED, DATED
 AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372