2001-08-31 00:00:00BUILDING PLAN REVIEW
 6215 S. FLAGLER DRIVE
 PERMIT # 01071037
 ARCH: SMITH & MOORE
 TEL: (561) 835- 1888
 FAX: (561) 832- 7015
  
 SBC= STANDARD BUILDING CODE 1997 ED.
 SBC*=AMENDMENTS /STANDARD BUILDING CODE
 FBC= FLORIDA BUILDING CODE (WILL BE
 ADOPTED JAN.1, 2002).
  
 1)- SBC* 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, A CURRENT SURVEY.
  
 2)- NOTE: SITE IS LOCATED IN A A-5 FLOOD
 ZONE. BFE IS TO BE 7'-6", CITY CODE.
  
 3)- SBC* 1804.2.7.2(3) REQUIRES SOILS
 TEST REPORT W/ MINIMUM BEARING VALUE.
  
 4)-FL. ENERGY CODE 600.1 ENERGY CODE
 CALCULATIONS INCLUDING MANUAL "J".
  
 5)- SBC 104.2.2*(2) SETS OF PLANS ARE
 REQUIRED FOR PERMIT APPLICATION.
  
 6)- (PCN) PROPERTY CONTROL NUMBER INDICA
 TES THAT THERE IS A EXISTING TWO STORY
 STRUCTURE, IS THIS TO STAY ON THIS LOT?
  
 7)- SHEET A-2 STRUCTURAL NOTES:
 SBC 1606.2.2. DESIGN CRITERIA ?
 CHAPTER 1606.
 ASCE 7-95 145 MPH BY INTERPERLATION
  
 8)- SBC 411.4.2: THE GARAGE DOESN'T MEET
 THE EXCEPTION, OVER 850 SQ. FT. REQUIRES
 (6) EXCHANGES OF AIR AN HOUR.
  
 9)- EXIT DOOR #120 REQUIRES A LANDING
 SEE SBC 1012.1.6.
  
 10)- SBC TABLE 600 NORTH ELEVATION TYPE
 V CONSTRUCTION ALLOWABLE OPEN AREA 40%
 THIS IS EXCEEDED. TYPE V CONSTRUCTION
 SEE SBC 411.2.9.
  
 11)- SHEET A-9AT THE GARAGE ELEVATION
 THERE IS A HASHED LINE, WHAT IS THIS
 INDICATION FOR?
  
 12)- SBC BY DEFINITION OF PENTHOUSE
 (1517.1.1.3.)IS A THREE STORY BUILDING.
 SBC TABLE 500 FOR TYPE V CONSTRUCTION RE
 QUIRES EITHER FIRESPRINKLERS OR 1 HOUR
 PROTECTION. THIS WILL ALLOW FOR A THREE
 STORY BUILDING.
  
 13)- SBC 705.6 WILL ALSO REQUIRE FLOOR
 CEILING ASSEMBLIES TO BE RATED, SHOW
 COMPLIANCE WITH PENETTRATIONS OF HORIZON
 TAL ASSEMBLIES.
  
 14)- ELEVATOR PLEASE PROVIDE THE MANUFAC
 TURERS SPECIFICATIONS.SHOW COMPLIANCE
 WITH SBC SECTION 3003.
  
 15)- MANUFACTUREED FIREPLACES SBC 2806
 FALSE FIREPLACES 2807. MANUFACTURES
 SPECIFICATION, FRESH AIR INTAKES RE-
 QUIRED & SHOW COMPLIANCE WITH THE ENERGY
 CODE.
  
 16)- ADDITIONAL INFOFRMATION REQUIRED
 SBC 2114 INFORMATION REGARDING THE SIZ-
 ING OF THE FIREPLACE FIREBOX NOT GIVEN,
 WIDTH & DEPTH OF FIREBOX. FLUE SIZING OF
 THE CHIMNEY ( FIGURE 2114.3.4)
  
 17)- SBC 1606.2.6.2COMPONENTS & CLADDING
 ALL GLAZED OPENINGS WILL REQUIRE WINDOW
 & DOOR BUCK ATTACHMENT DETAILS, ALSO FOR
 THE GARAGE DOORS.
  
 18)- SBC 1606.4.1/ 1707.4.1. ALL GLAZED
 OPENINGS WILL REQUIRE TESTING FOR WIND
 BORNE DERIS, LARGE MISSLE IMPACT RESIS-
 TANCE TESTING. OPENINGS THAT DONOT HAVE
 THIS APPROVAL WILL REQUIRE APPROVED
 STORM SHUTTERS EITHER SBCCI REPORT OR
 DADE COUNTY TESTING REPORTS ARE ACCEPTED
 (2) COPIES OF SAID REPORT WILL BE
 REQUIRED. A INSTALLATION SCHEDULE & KEY
 PLAN WILL ALSO BE REQUIRED, SEE ATTACH-
 MENT.
  
 19)- ROOF COVERINGS: SBC 1707.5 CLAY /
 CONCRETE ROOF TILE TESTING FOR 110 HPH
 WIND ZONE.
  
 20)- SBC 2405.2 SAFETY GLASS REQUIREMENT
 SEE MASTER BATH TUB, SHOWER DOORS, SWING
 DOORS,& SIDELIGHTS.
  
 21)- FL S.S.515 -TO TIE TO POOL PERMIT:
 RESIDENTIALSWIMMING POOL SAFETY ACT.
  
 22)- COUNTY IMPACT FEES DO AT TIME OF
 PERMIT ISSUANCE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412