| 2001-08-27 00:00:00 | BUILDING PLAN REVIEW: |
| | PERMIT: 01071019 |
| | ADDRESS: 9042 LAKES BLVD |
| | CONT: STATHIS CONSTRUCTION |
| | TEL: (954) 275-1337 |
| | |
| | 1)- SHEET A-3 DETAIL #3, ADD. INFO. RE- |
| | QUIRED. IS THIS A EXISTING COLUMN OR A |
| | NEW COLUMN? LOADS IMPOSED? A FOUNDATION |
| | REQUIRED? |
| | |
| | 2)- SHEET A-6 SHOWS A COLUMN WITH A MID- |
| | POINT BEARING POINT, WHERE IS THIS APPLI |
| | CATION USED? THIS SAME DETAIL REFRENCES |
| | (3) USES, A SINGGLE, DOUBLE & TRIPLE |
| | MEMBER TRUSS? |
| | |
| | 3)- SHEET A-6 DETAIL #22 NOTES THAT |
| | 1X2, 1X4 BUCKS WILL BE ATTACHED WITH "T" |
| | NAILS NO LENGTH IS GIVEN FOR THE NAIL |
| | OR MINIMUM EMBEDMENT. |
| | |
| | 4)- A-6 DETAIL"A" NO INSILATION INFOR. |
| | IS GIVEN FOR ABOVE THE GARAGE CEILING. |
| | |
| | 5)- SBC 104.2.2 ADD INFO. REQUIRED MISS- |
| | ING THE 2ND STORY ROOF FRAMING PLAN, |
| | TRUSS, GIRDER LOADS,VERTICAL / HORIZONT- |
| | AL AND GRAVITY LOADS TO BE RESISTED. |
| | |
| | 6)- SBC 104.2.2 ADD INFO REQUIRED, SHEET |
| | A-3,A-4 & A-5 INFORMATIN ON THE CANTI- |
| | LEVERED TRUSS ASSEMBLY WITH 4" DROP. |
| | |
| | 7)- MISSING IS A PRODUCT APPROVAL REPORT |
| | FOR THE SKYLIGHT, GLAZED OPENINGS RE- |
| | QUIRE LARGE MISSLE TESTING IF LOCATED |
| | LESS THAN 30' ABOVE GRADE. SBCCI OR DADE |
| | COUNTY REPORTS ARE ACCEPTED. |
| | |
| | 8)- SBC 2309.6 ATTIC ACCESS FOR THE |
| | 2ND FLOOR 22" X 36". |
| | |
| | 9)- SBC 2309.7 SOFFIT VENTING INFO? |
| | |
| | 10)- COUNTY IMPACT FEES |
| | |
| | 11)- PERMIT APPLICATION GIVE THE SQUARE |
| | FOOTAGE OF ADDITION? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |