| Notes |
| Date |
Text |
| 2001-10-16 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) THIRD NOTICE. PAGE A-4 DETAIL 4, | | | SINK TO COMPLY WITH FACBC-97 SEC 4.24. | | | SECTION 4.24.2 HEIGHT, 4.24.3 KNEE | | | CLEARANCE, 4.24.4 DEPTH, 4.24.5 CLEAR | | | FLOOR SPACE, 4.24.6 EXPOSED PIPES AND | | | 4.24.7 FAUCETS. PLEASE SHOW COMPLIANCE | | | WITH SECTION 4.24 ON DETAIL 4. | | | | | | 2) THIRD NOTICE. PAGES P1 & P2, FLAT | | | DRAWING ROOM 102, SHOW FLOOR SINK NOT | | | FUNNEL DRAIN. SANITARY RISER DIAGRAM, | | | SHOW FLOOR SINK NOT FUNNEL FLOOR DRAIN | | | FOR PAN DRAIN/RELIEF VALVE DISCHARGE. | | | | | | 3) THIRD NOTICE. PAGE P-2 WATER RISER | | | ISOMETRIC. SHOW PROPER PLACEMENT FOR | | | WATER HAMMER ARRESTORS. THEY SHALL BE | | | INSTALLED NEAR SOURCE OF VALVE NOT AT | | | TOP OF DROP AS SHOWN. INSTALL PER MANU- | | | FACTURE'S INSTRUCTIONS AND WH-PDI 201. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|