Plan Review Notes
Plan Review Notes For Permit 01070988
Permit Number 01070988
Review Stop P
Sequence Number 4
Notes
Date Text
2001-10-16 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) THIRD NOTICE. PAGE A-4 DETAIL 4,
 SINK TO COMPLY WITH FACBC-97 SEC 4.24.
 SECTION 4.24.2 HEIGHT, 4.24.3 KNEE
 CLEARANCE, 4.24.4 DEPTH, 4.24.5 CLEAR
 FLOOR SPACE, 4.24.6 EXPOSED PIPES AND
 4.24.7 FAUCETS. PLEASE SHOW COMPLIANCE
 WITH SECTION 4.24 ON DETAIL 4.
  
 2) THIRD NOTICE. PAGES P1 & P2, FLAT
 DRAWING ROOM 102, SHOW FLOOR SINK NOT
 FUNNEL DRAIN. SANITARY RISER DIAGRAM,
 SHOW FLOOR SINK NOT FUNNEL FLOOR DRAIN
 FOR PAN DRAIN/RELIEF VALVE DISCHARGE.
  
 3) THIRD NOTICE. PAGE P-2 WATER RISER
 ISOMETRIC. SHOW PROPER PLACEMENT FOR
 WATER HAMMER ARRESTORS. THEY SHALL BE
 INSTALLED NEAR SOURCE OF VALVE NOT AT
 TOP OF DROP AS SHOWN. INSTALL PER MANU-
 FACTURE'S INSTRUCTIONS AND WH-PDI 201.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377