2001-09-26 00:00:00DENIED
 REFERENCE SPC-94-FACBC-97
  
 1) PAGE A-4 PREVIOUS 2 PLAN REVIEW
 COMMENTS NOT ADDRESSED. ( 8-6 & 8-31)
 PLEASE SHOW COMPLIANCE WITH FACBC-97 SEC
 4.24 AT LOUNGE SINK DETAIL.
  
 2) PAGE P-2 PREVIOUS PLAN REVIEW COMMENT
 NOT ADDRESSED (8-31). SANITARY RISER DIA
 GRAM TO SHOW FLOOR SING, NOT FUNNEL
 FLOOR DRAIN FOR PAN DRAIN - RELIEF LINE
 DISCHARGE.
  
 3) PAGE P-2 PLUMBING SPECIFICATIONS #18.
 WATER HAMMER ARRESTORS TO COMPLY WITH
 MANUFACTURES INSTALLATION INSTRUCTIONS
 AND WH-PDI 201. SHOW PROPER INSTALLATION
 NOT AT TOP OF DROP AS SHOWN ON WATER
 RISER DIAGRAM.
  