2001-09-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070988
 1515 N FLAGLER DRIVE # 130
 CONT: CATALFUMO
 LORI: 307- 4836
  
 1)- PLANS SHEET A-3 DETAIL 6-A, INDICATE
 THE USE OF A WATER CURTAIN WITH THE
 REFRENCE NER # 516 REPORT. IN THIS RE-
 PORT ARE INSTALLATION INSTRUCTIONS
 (4.1 SPRINKLER ORIENTATION) THE REPORT
 MAKES IT CLEAR THAT AT LEAST A 36" PONY
 WALL SHALL BE REQUIRED ABOVE THE FINISH
 FLOOR, AS INSTUCTED BY THE MANUFACTURERS
 INSTALLATION MANUAL.
 CONDITIONS OF USE (7.8) GLAZING ASS-
 EMBLIES ARE REQUIRED TO BE EQUIPPED WITH
 A SOLID PARTIAL WALL AT LEAST 36" ABOVE
 THE FINISH FLOOR, AS INSTRUCTED BY THE
 MANUFACTURERS INSTALLATION MANUAL OR BY
 APPROVED ALTERNATE PROTECTION MEASURES.
 A COPY OF THE REPORT WILL BE ATTACHED.
  
 2)- SHEET A-3 DETAIL 9 MAKES REFRENCE TO
 ATTACHMENT OF A SOFFIT TO THE DECK ABOVE
 BUT DOESN'T GIVE THE SPACING OR TYPE OF
 FASTENER?
  
 3)- SHEET A-1 FINISH SCHEDULE PUBLIC
 RESTROOMS SBC 1204.2 THE WALLS & FLOORS
 OF PUBLIC RESTROOMS SHALL BE LINED WITH
 AN NONABSORBANT MATERIAL TO THE HEIGTH
 OF 4'-0".
  
 4)- FL ACCESS CODE 1997 4.5 FLOOR SUR-
 FACES ALONG ACCESSIBLE ROUTES AND IN ACC
 ESSIBLE ROOMS & SPACES INCLUDING FLOORS
 WALKS, RAMPS STAIRS, SHALL BE STABLE,
 FIRM& SLIP-RESISTANT. ADDAGG A STATIC
 COEFFICIENT OF FRICTION OF 6.0 IS
 RECOMMENDED FOR ACCESSIBLE ROUTES AND
 0.8 FOR RAMPS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412.