| Plan Review Notes For Permit 01070988 |
| Permit Number |
01070988 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-06 00:00:00 | DENIED; | | | | | | 1.PAGE A-4 LOUNGE ROOM #112. SHALL MEET | | | FACBC REQUIREMENTS SEC. 4.24 THRU | | | 4.24.7. | | | | | | 2.EXTEND RELIEF AND PAN DRAIN TO THE | | | OUTSIDE OR INTO A FLOOR SINK WITH A | | | TRAP PRIMER SEC. 507.8.4. | | | | | | 3.WATER HEATER DETAIL (NOTE) 2" HIGH | | | DRAIN PAN PROVIDE (1") DRAIN NOT 3/4". | | | | | | | | | 4.PAGE P-2 (WATERRISER) PLEASE SIZE | | | ALL PIPES TO WATER HEATER. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|