| Plan Review Notes For Permit 01070987 |
| Permit Number |
01070987 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-09-06 00:00:00 | PASSED/PROVISO | | | | | | 1) N-36 VACUUM BREAKER INSTALLED 6" | | | ABOVE FLOOD RIM LEVEL REQUIRED FOR | | | SUPPLY LINE TO (PRE FILTERS IF USED, OR | | | MILLIPORE UNIT. | | | 2) ALL INDIRECT WASTE SHALL DRAIN TO | | | A FLOOR SINK NOT FLOOR DRAIN, NOTE #1 | | | IN LABORATORY. SPC-94 SEC. 804.1/804.5. | | | 3) AIR HAMMER ARRESTORS SHALL BE INSTALL | | | ED PER MANUFACTURE'S INTSTALLATION IN- | | | STRUCTIONS. |
|