| Plan Review Notes For Permit 01070987 |
| Permit Number |
01070987 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | DENIED; | | | | | | 1.PAGE P-1 FLOOR SINKS ARE REQUIRED | | | WHERE BACKFLOW PREVENTORS ARE | | | INSTALLED AND MUST BE PRIMED. | | | 2.BACKFLOW TO BE READILY ACCESSIBLE | | | MOUNTED NO HIGHER THAN 4' OFF FLOOR. | | | SHOW DETAIL OF INSTALLATION AND | | | SPECIFY MODEL NUMBER AND SIZE. | | | 3.PAGE P-3 WATER HEATER DETAIL FLOOR | | | DRAIN SHALL BE FLOOR SINK. | | | 4.DRAIN FROM HEATER PAN SHALL BE 1" SPC | | | SEC. 507.7.8.2. | | | 5.WATER HAMMER ARRESTORS TO BE INSTALLED | | | PER MANUFACTORS SPECIFICATIONS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|