2001-08-02 00:00:00DENIED;
  
 1.PAGE P-1 FLOOR SINKS ARE REQUIRED
 WHERE BACKFLOW PREVENTORS ARE
 INSTALLED AND MUST BE PRIMED.
 2.BACKFLOW TO BE READILY ACCESSIBLE
 MOUNTED NO HIGHER THAN 4' OFF FLOOR.
 SHOW DETAIL OF INSTALLATION AND
 SPECIFY MODEL NUMBER AND SIZE.
 3.PAGE P-3 WATER HEATER DETAIL FLOOR
 DRAIN SHALL BE FLOOR SINK.
 4.DRAIN FROM HEATER PAN SHALL BE 1" SPC
 SEC. 507.7.8.2.
 5.WATER HAMMER ARRESTORS TO BE INSTALLED
 PER MANUFACTORS SPECIFICATIONS.