2001-08-09 00:00:00*******************PROVISO**************
  
  
 PLEASE CLARIFY HP-1, EXAM ROOM #4 (P123)
 INDICATES A 24" X 24" SUPPLY GRILL
 COMING OFF THE RETURN LINE.IS IT
 INTENDED FOR A RETURN OR SUPPLY?THE
 CFM LISTED ON THE SCHEDULE FOR HP-1 IS
 2200, YOU ONLY HAVE 1675 CFM WITHOUT
 COUNTING THE DROP IN QUESTION.IF YOU
 INCLUDE THE DROP IN QUESTION IT WILL
 BRING THE TOTAL CFM WILL BE BROUGHT UP
 TO 1875 CFM.
  
 NOTE:FAN SHUTDOWN WITH NOTIFICATION TO
 ALARM/STROBE OR BUILDING FIRE
 ALARM SYSTEM IN SYSTEMS GREATER
 THAN 2,000 CFM OR SERVING IN AN
 AREA OF EGRESS.(1997 SMC 406.1
 AND NFPA 90A 4-4.4.3 & 4-4.4.3.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.