| Plan Review Notes For Permit 01070987 |
| Permit Number |
01070987 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-09 00:00:00 | *******************PROVISO************** | | | | | | | | | PLEASE CLARIFY HP-1, EXAM ROOM #4 (P123) | | | INDICATES A 24" X 24" SUPPLY GRILL | | | COMING OFF THE RETURN LINE.IS IT | | | INTENDED FOR A RETURN OR SUPPLY?THE | | | CFM LISTED ON THE SCHEDULE FOR HP-1 IS | | | 2200, YOU ONLY HAVE 1675 CFM WITHOUT | | | COUNTING THE DROP IN QUESTION.IF YOU | | | INCLUDE THE DROP IN QUESTION IT WILL | | | BRING THE TOTAL CFM WILL BE BROUGHT UP | | | TO 1875 CFM. | | | | | | NOTE:FAN SHUTDOWN WITH NOTIFICATION TO | | | ALARM/STROBE OR BUILDING FIRE | | | ALARM SYSTEM IN SYSTEMS GREATER | | | THAN 2,000 CFM OR SERVING IN AN | | | AREA OF EGRESS.(1997 SMC 406.1 | | | AND NFPA 90A 4-4.4.3 & 4-4.4.3. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|