| Plan Review Notes For Permit 01070966 |
| Permit Number |
01070966 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY | | | THE FIRE PREVENTION BUREAU. | | | 2) THERE ARE APPROXIMATELY 130 SEATS | | | SHOWN ON THE DRAWINGS. | | | 3) PANIC HARDWARE REQUIRED ON ALL | | | REQUIRED EXIT DOORS. | | | 4) ITEM 8 NOTED ON THE PLANS INDICATES | | | A "SKYFOLD" MOTORIZED PARTITION WALL. | | | IT APPEARS THAT WHEN THIS ITEM IS | | | POSITIONED IT CUTS THE AREAS IN HALF. | | | ACCORDING TO THE ELECTRICAL PLANS, | | | PROPER NUMBER OF EXITS ARE NOT PRESENT | | | WHEN THESE DEVICES ARE IN PLACE. | | | PLEASE PROVIDE FLAMESPREAD ON THESE | | | ITEMS. | | | 5) TWO EXITS PER AREA ARE NEEDED SINCE | | | THIS SKYFOLD DEVICE LIMITS ACCESS TO | | | EXITS ALREADY IDENTIFIED ON THE PLANS. | | | 6) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 7) PLEASE IDENTIFY AISLE LOCATIONS. | | | 8) EXITS SHOULD BE REMOTE AS POSSIBLE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|