Plan Review Notes
Plan Review Notes For Permit 01070966
Permit Number 01070966
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:001) OCCUPANT LOAD TO BE DETERMINED BY
 THE FIRE PREVENTION BUREAU.
 2) THERE ARE APPROXIMATELY 130 SEATS
 SHOWN ON THE DRAWINGS.
 3) PANIC HARDWARE REQUIRED ON ALL
 REQUIRED EXIT DOORS.
 4) ITEM 8 NOTED ON THE PLANS INDICATES
 A "SKYFOLD" MOTORIZED PARTITION WALL.
 IT APPEARS THAT WHEN THIS ITEM IS
 POSITIONED IT CUTS THE AREAS IN HALF.
 ACCORDING TO THE ELECTRICAL PLANS,
 PROPER NUMBER OF EXITS ARE NOT PRESENT
 WHEN THESE DEVICES ARE IN PLACE.
 PLEASE PROVIDE FLAMESPREAD ON THESE
 ITEMS.
 5) TWO EXITS PER AREA ARE NEEDED SINCE
 THIS SKYFOLD DEVICE LIMITS ACCESS TO
 EXITS ALREADY IDENTIFIED ON THE PLANS.
 6) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 7) PLEASE IDENTIFY AISLE LOCATIONS.
 8) EXITS SHOULD BE REMOTE AS POSSIBLE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910