| 2001-07-25 00:00:00 | 1) PLEASE PROVIDE DETAILS ON 3M FIREWRAP | | | PLANNED FOR USE. PLEASE PROVIDE | | | MANUFACTURER'S INFORMATION WITH | | | REGARDS TO PROPER INSTALLATION. | | | 2) A MINIMUM 10 FOOT SEPARATION IS | | | REQUIRED BETWEEN EXHAUST AND SUPPLY AIR. | | | 3) WRONG PITCH NOTED ON PLANS FOR | | | EXHAUST DUCT. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SUPPRESSION SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|