Plan Review Notes
Plan Review Notes For Permit 01070730
Permit Number 01070730
Review Stop R
Sequence Number 6
Notes
Date Text
2002-02-11 00:00:00*************BUILDING DENIED************
  
 1) THE SITE SPECIFIC PRODUCT APPROVAL
 THAT WAS SUBMITTED FOR THE ENTRY DOOR IS
 NOT ACCEPTABLE. IT MUST BE SIGNED,
 SEALED AND DATED BY THE DESIGN
 PROFESSIONAL OF RECORD FOR THE STRUCTURE
 WHICH IS JOSEPH LATERZA.
  
 2) THE INFORMATION SUBMITTED, CHANGING
 THE SHAPE OF THE FRONT ENTRANCE STOOP
 FROM A RECTANGLE TO AN ARCH IS
 CONSIDERED A REVISION AND IS REQUIRED TO
 BE SUBMITTED AS A REVISION. THE DRAWINGS
 ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED BY THE DESIGN PROFESSIONAL OF
 RECORD, JOSEPH LATERZA.
 A SEPARATE PERMIT WILL BE REQUIRED FOR
 THE AWNING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202