| 2001-12-15 00:00:00 | TRUSSES |
| | DENIED |
| | |
| | 1) TRUSS DRAWINGS AND TRUSS LAYOUT MUST |
| | BE REVIEWED AND APPROVED BY THE DESIGNER |
| | OF RECORD FOR THE STRUCTURE. THIS IS |
| | REQUIRED TO BE INDICATED ON THE TRUSS |
| | LAYOUT ALONG WITH THE ORIGINAL SIGNATURE |
| | OF THE DESIGNER OF RECORD. |
| | |
| | 2) THE TRUSS LAYOUT IS REQUIRED TO HAVE |
| | THE TRUSS ENGINEER'S ORIGINAL SIGNATURE, |
| | EMBOSSED SEAL AND DATE IN ADDITION TO |
| | HIS TITLE BLOCK (NAME, NUMBER & ADDRESS) |
| | RUBBER SIGNATURE STAMPS ARE NOT |
| | ACCEPTABLE. |
| | |
| | 3) THE MEAN ROOF HEIGHT OF THE STRUCTURE |
| | IS 27 FEET PER DESIGN COMPLIANCE FORM BY |
| | ENGINEER OF RECORD. THE TRUSS DRAWINGS |
| | HAVE MEAN ROOF HEIGHTS OF 15 FEET AND |
| | 18.58 FEET. TRUSSES ARE REQUIRED TO BE |
| | ENGINEERED FOR MEAN ROOF HEIGHT OF THE |
| | STRUCTURE. PLEASE CORRECT. |
| | |
| | 4) THE TRUSS PACKAGE INDICATES TRUSSES |
| | FOR THE DORMERS AND THE PLANS SHOW 2X6 |
| | RAFTERS. A REVISION TO THE PLANS WHICH |
| | INDICATES TRUSSES AND THE TYPE OF TRUSS |
| | CONNECTORS REQUIRED TO RESIST THE LOADS |
| | MUST BE SUBMITTED. |
| | |
| | 5) THE PAGES LISTED ON THE INDEX SHEET |
| | AS NON. APP. AND SUBMITTED AS PART OF |
| | THE TRUSS PACKAGE MUST COMPLY WITH THE |
| | REQUIREMENTS OF 61G15-31.003. SOME OF |
| | THESE DRAWINGS REFERENCE THE WRONG CODE |
| | (1991 SSBCC) AND OTHERS DO NOT APPLY TO |
| | THIS PROJECT. PLEASE REMOVE PAGES THAT |
| | DO NOT APPLY AND THE ONES THAT REMAIN |
| | MUST COMPLY. PLEASE CLARIFY NON. APP. |
| | SEE COPY OF 61G15-31.003 ATTACHED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |