Plan Review Notes
Plan Review Notes For Permit 01070730
Permit Number 01070730
Review Stop R
Sequence Number 4
Notes
Date Text
2001-12-15 00:00:00TRUSSES
 DENIED
  
 1) TRUSS DRAWINGS AND TRUSS LAYOUT MUST
 BE REVIEWED AND APPROVED BY THE DESIGNER
 OF RECORD FOR THE STRUCTURE. THIS IS
 REQUIRED TO BE INDICATED ON THE TRUSS
 LAYOUT ALONG WITH THE ORIGINAL SIGNATURE
 OF THE DESIGNER OF RECORD.
  
 2) THE TRUSS LAYOUT IS REQUIRED TO HAVE
 THE TRUSS ENGINEER'S ORIGINAL SIGNATURE,
 EMBOSSED SEAL AND DATE IN ADDITION TO
 HIS TITLE BLOCK (NAME, NUMBER & ADDRESS)
 RUBBER SIGNATURE STAMPS ARE NOT
 ACCEPTABLE.
  
 3) THE MEAN ROOF HEIGHT OF THE STRUCTURE
 IS 27 FEET PER DESIGN COMPLIANCE FORM BY
 ENGINEER OF RECORD. THE TRUSS DRAWINGS
 HAVE MEAN ROOF HEIGHTS OF 15 FEET AND
 18.58 FEET. TRUSSES ARE REQUIRED TO BE
 ENGINEERED FOR MEAN ROOF HEIGHT OF THE
 STRUCTURE. PLEASE CORRECT.
  
 4) THE TRUSS PACKAGE INDICATES TRUSSES
 FOR THE DORMERS AND THE PLANS SHOW 2X6
 RAFTERS. A REVISION TO THE PLANS WHICH
 INDICATES TRUSSES AND THE TYPE OF TRUSS
 CONNECTORS REQUIRED TO RESIST THE LOADS
 MUST BE SUBMITTED.
  
 5) THE PAGES LISTED ON THE INDEX SHEET
 AS NON. APP. AND SUBMITTED AS PART OF
 THE TRUSS PACKAGE MUST COMPLY WITH THE
 REQUIREMENTS OF 61G15-31.003. SOME OF
 THESE DRAWINGS REFERENCE THE WRONG CODE
 (1991 SSBCC) AND OTHERS DO NOT APPLY TO
 THIS PROJECT. PLEASE REMOVE PAGES THAT
 DO NOT APPLY AND THE ONES THAT REMAIN
 MUST COMPLY. PLEASE CLARIFY NON. APP.
 SEE COPY OF 61G15-31.003 ATTACHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202