| 2002-04-10 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) THE MINIMUM FOOTING THICKNESS OF A |
| | MONOLITHIC SLAB ON GRADE IS 20 INCHES |
| | PER SSTD 10-97 SECT. 303.3.1. PLEASE |
| | CORRECT. |
| | |
| | 2) THE MINIMUM ANCHOR BOLT DIAMETER IS |
| | 5/8" WITH A MINIMUM OF 7" EMBEDMENT. THE |
| | WASHERS ARE REQUIRED TO BE 3"X 3"X 1/8" |
| | PER SSTD 10-97 SECT. 303.3.2. PLEASE |
| | CORRECT. |
| | |
| | 3) A DOUBLE LAYER OF 6X6 NO.10 WELDED |
| | WIRE FABRIC 3 FEET WIDE SHALL BE |
| | PROVIDED AROUND THE PERIMETER OF THE |
| | SLAB PER SSTD 10-97 SECT. 304.1.3. |
| | |
| | 4) INDICATE THE LOCATION OF HOLDDOWN |
| | CONNECTORS REQUIRED AT THE EXTERIOR |
| | SHEAR WALLS PER SSTD 10-97 SECT.305.4. |
| | |
| | 5) A MECHANICAL EXHAUST VENT TO THE |
| | EXTERIOR IS REQUIRED IN THE EXISTING |
| | BATHROOM IN WHICH THE WINDOW IS BEING |
| | REMOVED. |
| | |
| | 6) THE WEST ELEVATION OF THE ADDITION |
| | DOES NOT COMPLY WITH TABLE 600 OF THE |
| | 97 SBC FOR THE PERCENTAGE OF WALL AREA |
| | OPENINGS ALLOWED BASED ON THE INFO THAT |
| | WAS SUBMITTED. THE WALL AREA OF THE |
| | EXISTING STRUCTURE CAN BE USED IF THE |
| | OPENINGS (WINDOW, DOOR, ETC.) ARE |
| | INDICATED ON THE PLANS. TWENTY PERCENT |
| | OF THE WALL AREA (FLOOR TO CEILING HT.) |
| | IS ALLOWED AS OPENINGS BASED ON A |
| | DISTANCE OF 3'TO 10'TO THE PROPERTY |
| | LINE. |
| | |
| | 7) THE SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN IS REQUIRED |
| | ON THE DRAWINGS PER CITY OF W.P.B. |
| | AMENDMENTS TO THE 97 SBC SECT. 104.2.1. |
| | |
| | 8) THE NOTES FOR ROOF SHEATHING NAILING |
| | REQUIREMENTS ARE NOT CLEAR. IN ZONES 1& |
| | 2 THE REQUIRED NAIL SPACING IS 6" O.C. |
| | ON THE EDGES AND 6"O.C. INTERMEDIATE. IN |
| | ZONE 3 THE NAIL SPACING IS 4"O.C. AT THE |
| | EDGES AND 6"O.C. INTERMEDIATE. SEE CITY |
| | OF WPB AMENDMENTS TO 97 SBC SECT. 2306. |
| | PLEASE CLARIFY. |
| | |
| | 9)THE TOTAL NOMINAL THICKNESS FOR STUCCO |
| | ON METAL LATH OVER SOLID BASE IS 7/8" |
| | PER 97SBC SECT.2405.2.1 AND ASTM C 926. |
| | PLEASE CORRECT. |
| | |
| | 10) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - STRUCTURAL WINDOW MULLIONS THAT WILL |
| | BE USED TO CONNECT WINDOWS IN ADDITION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |