| 2002-04-04 00:00:00 | ***************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT NOTES FROM |
| | FIRST AND SECOND REVIEW ARE STILL NOT |
| | ADDRESSED???? |
| | |
| | 2)NOTE: PLEASE NOTE MISSING REQ`D BATH |
| | RECEPT PER 210-52D, ALSO ALL TO BE |
| | SHOWN AS GFI/GFI PROTECTED.210-8 |
| | |
| | 3)NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 4)NOTE: PLEASE NOTE THAT PANEL SCHEDULE |
| | AND LOAD CALCULATIONS,,,DO NOT CORRELATE |
| | PLEASE NOTE THAT THERE ARE MANY THINGS |
| | THAT DO NOT MATCH UP??? |
| | |
| | 5)NOTE: PLEASE NOTE THAT PLANS ARE NOTED |
| | THAT NO CENTRAL A/C IS EXISTING AND YET |
| | THEY ARE SHOWN ON LOAD CALCULATIONS????? |
| | PLEASE CLARIFY!!! IF NEW SHOW EQUIPMNET |
| | AND DISC`S PER 440-11. |
| | IF THERE IS NONE THEN PLEASE REMOVE. |
| | |
| | 6)NOTE: PANEL IS SHOWN TO BE 125A AS |
| | EXISTING AND ALSO SHOWN AS 150A AS EXIST |
| | ING??? WHICH ONE. ALSO SHOWN AS 15A |
| | ABOVE LOAD CALCS. |
| | |
| | 7)NOTE: PLEASE NOTE THAT BOTH SMALL |
| | APPLIANCE CIRCUITS ARE SHOWN AS 2000W`S |
| | PLEASE SEE 210-52B, 210-11C-1. |
| | |
| | 8)NOTE: PLEASE NOTE THAT THERE IS |
| | NOTHING SHOWN FOR "HOW" DETACHED GARAGE |
| | IS FED??? MEANS OF DISC? 225-31, |
| | GROUNDING??250-32 |
| | |
| | 9)NOTE: PLEASE HAVE PLANS PLACED INTO |
| | TWO SET FOR REVIEW. PLEASE KEEP ALL OLD |
| | SETS SEPARATE. PLEASE DATE PLANS AS REQ` |
| | D. |
| | PLEASE CLARIFY PROVIDE INFORMATION ON |
| | PERSON WHO DREW PLANS. ARCH/OR DRAFTSMAN |
| | PLEASE NOTE THAT IF DONE BY AN ARCH, |
| | THEN PLANS MUST BE SIGNED AND SEALED BY |
| | THAT PERSON. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE NOTE ONCE AGAIN, IF THERE |
| | ARE ANY QUESTIONS,,,,,,, PLEASE CALL!!!! |
| | IF A MEETING IS NEEDED TO GO OVER PLANS |
| | AND CODE ISSUES,,,,, PLEASE CALL. |
| | |