| 2001-07-31 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) THE ENGINEER'S TITLE BLOCK IS |
| | REQUIRED ON EACH SHEET OF THE PLANS |
| | THATARE SIGNED AND SEALED BY HIM. |
| | |
| | 3) THE BUCK DETAILS AND WALL DETAIL ARE |
| | ILLEGIBLE. PLEASE PROVIDE PLANS THAT |
| | ARECLEAR AND READABLE. |
| | |
| | 4) INDICATE METHODS OF ATTACHMENT FOR |
| | SECURING FRAME WALLS AND CONCRETE FOOT- |
| | INGS TO EXISTING STRUCTURE. |
| | |
| | 5) PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL |
| | J)AS REQUIRED BY THE 1997 FLORIDA |
| | ENERGYEFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION. |
| | |
| | 6) INDICATE SPECIAL ROOF SHEATHING |
| | NAILING ZONES COMPLYING WITH SECTION |
| | 2306 OF THE CITY AMENDMENTS TO THE 97 |
| | SBC. |
| | |
| | 7) PROVIDE GABLE END BRACING DETAILS. |
| | |
| | 8) INDICATE HOW ATTIC ACCESS TO NEW |
| | ADDITION WILL BE ACHIEVED. |
| | |
| | 9) THE ROOF PLANS INDICATE # 11 |
| | CONNECTORS FROM THE SCHEDULE FOR |
| | ATTACHING THE TRUSSES TO THE WALLS. |
| | THESE CONNECTORS ARE FOR WOOD TRUSS TO |
| | CONCRETE BEAM CONNECTIONS. PLEASE |
| | INDICATE THE APPROPRIATE CONNECTORS |
| | WHICH ARE CAPABLE OF WITHSTANDING THE |
| | CALCULATED LOADS. |
| | |
| | 10) INDICATE THE POSITIVE AND NEGATIVE |
| | PRESSURES FOR ALL EXTERIOR WINDOW AND |
| | DOOR OPENINGS OF ADDITION AND DETACHED |
| | GARAGE. |
| | |
| | 11) INDICATE THE SPECIFICATE TYPES OF |
| | CONNECTORS THAT WILL BE USED TO PROVIDE |
| | A CONTINOUS TIE FROM THE FOUNDATION TO |
| | THE ROOF. |
| | |
| | 12) INDICATE THE TYPES AND SIZES OF THE |
| | WINDOWS AND DOORS ON THE PLANS. |
| | |
| | 13) TABLE 600 IN THE 97 SBC IS USED TO |
| | DETERMINE THE PERCENTAGE OF WALL AREA |
| | THAT IS ALLOWED AS OPENINGS BASED ON |
| | THEDISTANCE TO THE PROPERTY LINE OR |
| | ASSUMEDPROPERTY LINE. PLEASE PROVIDE |
| | BOTH SIDE AND REAR ELEVATIONS FOR THE |
| | ADDITION ANDALL FOUR ELEVATIONS FOR THE |
| | GARAGE. |
| | |
| | 14) PROVIDE TWO (2) LEGIBLE COPIES OF |
| | THE SURVEY, WHICH INDICATE THE |
| | DISTANCESTO THE PROPERTY LINES AND THE |
| | DISTANCE |
| | BETWEEN THE ADDITION AND THE GARAGE. |
| | |
| | 15) THE BEDROOM WINDOW MUST COMPLY WITH |
| | EGRESS REQUIREMENTS. 97 SBC SEC. 1005.4 |
| | |
| | 16) SAFETY GLASS IS REQUIRED IN THE |
| | BATHROOM WINDOWS IF LOCATED LESS THAN |
| | 60" |
| | ABOVE THE TUB DRAIN INLET. |
| | |
| | 17) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - ROOFING MATERIAL |
| | - GARAGE DOOR |
| | - WINDOWS (THE ONE SUBMITTED IS |
| | EXPIRED)- SIDE SWING DOOR (THE ONE |
| | SUBMITTED |
| | DOES NOT CORRESPOND TO THE PLANS) |
| | NOTE: TWO COPIES ARE REQUIRED |
| | |
| | 18) THE BOTTOM OF THE FOOTINGS SHALL BE |
| | A MINIMUM OF 12" BELOW FINISH GRADE. |
| | 97 SBC SEC.1804.1.3 |
| | |
| | 19) WHERE LATH AND STUCCO IS APPLIED |
| | OVER THE EXTERIOR OF WOOD FRAME |
| | CONSTRUCTION, AN APPROVED WEEP SCREED |
| | (STUCCO STOP) PLACED NOT LESS THAN 6" |
| | ABOVE FINISH GRADE SHALL BE USED TO |
| | TERMINATE STUCCO AT THE BASE OF THE |
| | WALL2304.2.5 OF CITY AMENDEMENTS TO 97 |
| | SBC. |
| | |
| | 20) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF |
| | ANCHORS TO BE USED FOR STORM PANELS. |
| | NOTE: MISSLE IMPACT PROTECTION IS |
| | REQUIRED FOR ALL GLAZED EXTERIOR |
| | OPENINGS. |
| | |