| 2001-08-02 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT RECEPTS IN GAR |
| | ARE TO BE GFI/GFI PROTECTED PER 210-8. |
| | |
| | 2)NOTE: PLEASE SUBMIT INFORMATION FOR |
| | MEANS OF DISCONNECT AT DETACHED |
| | STRUCTURE.225-31 |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | PLEASE SUBMIT A PANEL SCHEDULE FOR |
| | REQ`DCIRCUITS (EXISTING AND NEW) |
| | |
| | 5)NOTE: PLEASE CLARIFY NEW A/C SHOWN ON |
| | RISER DIAGRAM? PLEASE SHOW ON PLANS AND |
| | PROVIDE A/C RECEPT AND DISC`S PER |
| | 440-11AND 309.1 (MECH CODE) |
| | |
| | 6) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 7) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | MISSING REAR. |
| | |
| | PLEASE MAKE NOTE THAT IF THERE IS GOING |
| | TO BE ANY CATV AND/OR TELEPHONE IN NEW |
| | ADDITION, THEN IT NEEDS TO BE DRAWN ON |
| | PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |