Plan Review Notes
Plan Review Notes For Permit 01070628
Permit Number 01070628
Review Stop R
Sequence Number 3
Notes
Date Text
2001-12-05 00:00:00TRUSSES
 DENIED
  
 1) SIMPSON HGT-2 TIE DOWN REQUIRES (2)
 3/4" DIAMETER ANCHORS WITH A 5"
 EMBEDMENT DEPTH.
  
 2) SIMPSON HHETA 20 REQUIRES (17) 10D X
 1 1/2" NAILS FOR A 2310# UPLIFT CAPACITY
  
 3) HGT-2 IS FOR A TWO MEMBER TRUSS AND
 FG1 IS A THREE MEMBER TRUSS. AN HGT-3
 WITH (2) 3/4" DIAMETER BOLTS WITH 5"
 EMBEDDMENT IS FOR THREE MEMBER TRUSSES.
  
 4) HETAL 12 WITH (10) 10D X 1 1/2" NAILS
 HAVE AN UPLIFT CAPACITY OF 895#, NOT
 1095# AS STATED IN LETTER.
  
 PLEASE REVISE LETTER AND RESUBMIT.