Plan Review Notes
Plan Review Notes For Permit 01070620
Permit Number 01070620
Review Stop R
Sequence Number 1
Notes
Date Text
2001-08-04 00:00:00*************BUILDING UNSAT*************
  
 1)STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 2) SURVEY AND PLANS DO NOT CORRESPOND
 WITH EACH OTHER. SURVEY INDICATES A
 CATALINA MODEL AND PLANS ARE FOR A
 LAGUNA MODEL. SUBMITED CORRECTED SURVEY.
  
 3) DUE TO INCORRECT SURVEY, THE
 PERCENTAGE OF EXTERIOR OPENINGS ALLOWED
 BY 97 SBC TABLE 600 COULD NOT BE
 CALCULATED.
  
 4) THE PLANS HAVE AN EXTRA SHEET A-2.
 PLEASE REMOVE ONE OF THEM FROM EACH SET.
  
 5) THE WALL SECTION ON A-2 INDICATES A
 FOOTER WITH A 20" DEPTH THE FOOTER
 SCHEDULE ON A-1 GIVES FOOTER DEPTH AS
 18". PLEASE REVISE SO THAT PLANS ARE
 CONSISTENT.
  
 6) THE FOOTINGS FOR THE 10" COLUMNS AT
 THE ENTRY ARE INDICATED AS F-8
 MONOLITHIC PADS BUT APPEAR TO BE F-8A
 CONCRETE PADS. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202