Plan Review Notes
Plan Review Notes For Permit 01070616
Permit Number 01070616
Review Stop R
Sequence Number 1
Notes
Date Text
2001-08-02 00:00:00*************BUILDING UNSAT*************
  
 1) STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 2) THE SURVEY DOES NOT CORRESPOND TO THE
 PLANS. PROVIDE SURVEY WITH CORRECT MODEL
 SHOWN ON LOT.
  
 3) WALL SECTION DETAIL ON SHEET A-2 HAS
 A 20" DEPTH FOOTER AND FOOTING SCHEDULE
 ON A-1 INDICATES AN 18" FOOTER DEPTH FOR
 F-1. PLEASE CORRECT.
  
 4) DUE TO INCORRECT SURVEY, PERCENTAGE
 OF ALLOWABLE WALL OPENINGS COULD NOT BE
 VERIFIED. (97 SBC TABLE 600)
  
 5) TRUSS ENGINEER TO BE SUPPLIED WITH
 INFORMATION ON A/C EQUIPMENT THAT IS
 BEING HUNG FROM TRUSSES TO INSURE THAT
 TRUSSES ARE DESIGN TO SUPPORT IMPOSED
 LOADS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202