| Plan Review Notes For Permit 01070616 |
| Permit Number |
01070616 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) STRUCTURE IS LOCATED IN AN "A8" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL | | | BE REQUIRED. | | | | | | 2) THE SURVEY DOES NOT CORRESPOND TO THE | | | PLANS. PROVIDE SURVEY WITH CORRECT MODEL | | | SHOWN ON LOT. | | | | | | 3) WALL SECTION DETAIL ON SHEET A-2 HAS | | | A 20" DEPTH FOOTER AND FOOTING SCHEDULE | | | ON A-1 INDICATES AN 18" FOOTER DEPTH FOR | | | F-1. PLEASE CORRECT. | | | | | | 4) DUE TO INCORRECT SURVEY, PERCENTAGE | | | OF ALLOWABLE WALL OPENINGS COULD NOT BE | | | VERIFIED. (97 SBC TABLE 600) | | | | | | 5) TRUSS ENGINEER TO BE SUPPLIED WITH | | | INFORMATION ON A/C EQUIPMENT THAT IS | | | BEING HUNG FROM TRUSSES TO INSURE THAT | | | TRUSSES ARE DESIGN TO SUPPORT IMPOSED | | | LOADS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|