| Plan Review Notes For Permit 01070604 |
| Permit Number |
01070604 |
|
| Review Stop |
R |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-12-05 00:00:00 | TRUSSES | | | DENIED | | | | | | 1) LETTER FROM ENGINEER MUST HAVE THE | | | EMBOSSED SEAL OF THE ENGINEER. | | | | | | 2) CONNECTOR HETAL 20 (EMBEDDED ANCHOR) | | | REQUIRES (20) 10D X 1 1/2" NAILS FOR | | | UPLIFT CAPACITY OF 1890#. LETTER STATES | | | (15) NAILS. | | | | | | 3) THE INTERIOR BEARING OF SG2 IS AT | | | JOINT #15 NOT #21. THE TRUSS WEBS VEE AT | | | THIS POINT(SEE TRUSS DRAWING), WHICH | | | WILL NOT PROVIDE ADEQUATE NAILING FOR | | | MST136 STRAP. PLEASE ADVISE AS TO HOW | | | THESE WILL ATTACH TO TRUSS. | | | | | | PLEASE MAKE CORRECTIONS TO LETTER AND | | | RESUBMIT. | | | | | | SAME NOTES APPLY TO 01071616 AND | | | 01070611. |
|