Plan Review Notes
Plan Review Notes For Permit 01070604
Permit Number 01070604
Review Stop R
Sequence Number 4
Notes
Date Text
2001-12-05 00:00:00TRUSSES
 DENIED
  
 1) LETTER FROM ENGINEER MUST HAVE THE
 EMBOSSED SEAL OF THE ENGINEER.
  
 2) CONNECTOR HETAL 20 (EMBEDDED ANCHOR)
 REQUIRES (20) 10D X 1 1/2" NAILS FOR
 UPLIFT CAPACITY OF 1890#. LETTER STATES
 (15) NAILS.
  
 3) THE INTERIOR BEARING OF SG2 IS AT
 JOINT #15 NOT #21. THE TRUSS WEBS VEE AT
 THIS POINT(SEE TRUSS DRAWING), WHICH
 WILL NOT PROVIDE ADEQUATE NAILING FOR
 MST136 STRAP. PLEASE ADVISE AS TO HOW
 THESE WILL ATTACH TO TRUSS.
  
 PLEASE MAKE CORRECTIONS TO LETTER AND
 RESUBMIT.
  
 SAME NOTES APPLY TO 01071616 AND
 01070611.