| Plan Review Notes For Permit 01070604 |
| Permit Number |
01070604 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-10-30 00:00:00 | TRUSSES | | | UNSAT | | | | | | 1) FOR TRUSS S13 THE TRUSS DRAWINGS | | | INDICATE AN UPLIFT OF 1600# AT JOINT 13. | | | SHEET A-3 OF THE PLANS INDICATE AN HC10 | | | CONNECTOR RATED FOR 1325# OF UPLIFT. | | | | | | 2) FOR TRUSS S14 THE TRUSS DRAWINGS | | | INDICATE AN UPLIFT OF 1650# AT JOINT 13. | | | SHEET A-3 OF THE PLANS INDICATE AN HC10 | | | CONNECTOR RATED FOR 1325# OF UPLIFT. | | | | | | 3) FOR TRUSS SG2 THE TRUSS DRAWINGS | | | INDICATE 1860# OF UPLIFT AT JOINT 21 AND | | | THE PLANS INDICATE A HETAL-16 RATED FOR | | | 1365# OF UPLIFT. | | | THE TRUSS DRAWINGS INDICATE 4200# UPLIFT | | | AT JOINT 15 AND PLANS HAVE LSTA-24 RATED | | | FOR 1295# OF UPLIFT. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | THESE COMMENTS APPLY TO THE TRUSSES FOR | | | PERMIT NUMBERS 01070611, 01070616 AND | | | 01071305. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|