Plan Review Notes
Plan Review Notes For Permit 01070604
Permit Number 01070604
Review Stop R
Sequence Number 1
Notes
Date Text
2001-08-04 00:00:00*************BUILDING UNSAT*************
  
 1) STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 2) THE PERCENTAGE OF WALL AREA ALLOWED
 AS OPENINGS PER THE 97 SBC TABLE 600 IS
 EXCEEDED AT REAR OF STRUCTURE. BASED ON
 THE DISTANCE TO THE PROPERTY LINE 40% OF
 THE WALL AREA IS ALLOWED AS OPENINGS.
  
 3) THE FOOTINGS FOR THE 10" COLUMNS AT
 THE ENTRY ARE DESIGNATED AS F-8 WHICH
 ARE MONOLITHIC PADS BUT APPEAR TO BE
 F-8A CONCRETE PADS. PLEASE REVIEW AND
 CORRECT.
  
 4) WALL SECTION ON SHEET A-2 SHOWS A
 FOOTER WITH A DEPTH OF 20" AND FOOTER
 SCHEDULE ON SHEET A-1 INDICATES AN 18"
 FOOTER DEPTH AT F-1. PLEASE REVISE SO
 THAT SHEETS ARE CONSISTENT.
  
 5) ADVISE TRUSS ENGINEER THAT A/C
 EQUIPMENT WILL BE SUPPORTED BY TRUSSES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202