| Plan Review Notes For Permit 01070579 |
| Permit Number |
01070579 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-08-29 00:00:00 | PLAN REVIEW | | | PERMIT # 01070579 | | | 423 4TH ST | | | CONT: SISCA CONSTRUCTION | | | TEL: (561) 309-7175 | | | | | | 1)- 3RD FLOOR STAIRS TO THE EXTERIOR: | | | SBC 1007.4.2."THE WIDTH OF THE LANDING | | | SHALL BE NOT LESS THAN THE WIDTH OF THE | | | STAIRWAY THEY SERVE. EVERY LANDING SHALL | | | HAVE A MINIMUM DIMENSION IN THE DIRECTIO | | | N OF TRAVEL EQUAL TO THE WIDTH OF THE | | | STAIRWAY." THE FIRE MARSHALL USES THE | | | LIFE SAFETY CODE, THE BUILDING DEPART- | | | MENT USES THE STANDARD BUILDING CODE. WH | | | EN THERE IS A DIFFERENCE IN CODES THE | | | MOST STRINGENT CODE IS ENFORCED. | | | | | | 2)-FLOOR PENETRATIONS, SBC705.6.1 | | | THROUGH PENETRATIONS OF FIRE RATED HORI- | | | ZONTAL ASSEMBLIES (FLOOR) SHALL COMPLY | | | WITH 705.6.1.1 OR 705.6.1.2. SHOW COMPLI | | | ANCE. THERE ISVERTICAL PIPING RAIN | | | WATER LITERS THAT ARE ON THE 3RD & 2ND | | | FLOORS, IF THEY DO NOT GO THROUGH THE | | | FLOOR WHERE DO THEY GO ? | | | | | | AREA OF REFUGE SBC 1004.3.2.1 SHOW COM- | | | PLIANCE, A COPY OF THE CODE COMMENTARY | | | IS ATTACHED TO GIVE EXAMPLES OF AREA OF | | | REFUGE. | | | | | | FLORIDA ACCESIBILITY CODE 4.1.6(K III) | | | 3RD FLOOR STAIR TO THE ROOF PROVIDE | | | VERTICAL ACCESSIBILITY. |
|