| Plan Review Notes For Permit 01070579 |
| Permit Number |
01070579 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-02 00:00:00 | DENIED; | | | 1.HANDICAP TOILET MEASUREMENT OFF FINISH | | | WALL SHALL BE 18". FACBC FIG.28. | | | 2.DRINKING FOUNTAIN TO COMPLY WITH 4.1.3 | | | AND 4.15. | | | 3.MEN'S ROOM SHOULD HAVE A FLOOR DRAIN | | | ALSO. | | | 4.FLOOR DRAINS SHALL HAVE TRAP PRIMERS | | | SPC SEC 409.4.1.1. | | | 5.DRINKING FOUNTAIN MAXIMUM HIGHTH TO | | | ORIFICE IS 36" FACBC FIG. 27(A). | | | 6.NOTE 8, ALL WATER HAMMER ARRESTERS TO | | | BE ENGINEERED PER SPC SEC. 607.8.2 | | | AND 607.8.3. LOCATE PER MANUFACTOR | | | RECOMMENDATIONS. | | | 7.NOTE 10, BOTTLED WATER COOLER IS NOT | | | A PLUMBING FIXTURE AND CAN NOT BE USED | | | AS AN ALTERNATE METHOD. SEE TABLE 407 | | | UNDER MISCELLANEOUS FIXTURES. ALSO SEE | | | CHAPTER 2 DEFINITIONS "PLUMBING | | | FIXTURES. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|