| 2001-08-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 0107579 |
| | 423 4TH STREET 2ND & 3RD FL |
| | |
| | CONT: SISCA CONSTRUCTION |
| | TEL: (561) 309-7175 |
| | |
| | 1)- EXTERIOR STEEL STAIRS : SBC 1006.2.4 |
| | EXTERIOR STAIRS SHALL BE SEPERATED FROM |
| | THE INTERIOR OF THE BUILDINGBY WALLS |
| | WITH A FIRE RESISTANCE RATING OF NOT |
| | LESS THAN 1 HR, WITH FIXED OR SELF-CLOS- |
| | ING OPENING PROTECTIVES AS REQUIRED FOR |
| | ENCLOSED STAIRS.THIS PROTECTION SHALL |
| | EXTEND VERTICALLY FROM THE GROUND TO A |
| | POINT 10 FT. ABOVE THE UPPER MOST LAND- |
| | ING OR THE ROOF LINE, WHICHEVER IS LOWER |
| | AND HORIZONTALLY 10 FT. FROM EACH SIDE |
| | OF THE STAIRWAY. OPENINGS WITHIN 10 FT |
| | HORIZONTAL EXTENSION OF THE PROTECTED |
| | WALLS BEYOND THE STAIRWAY SHALL BE |
| | FIXED 3/4 HR ASSEMBLIES. |
| | |
| | 2)- 3RD FLOOR STAIRS TO EXTERIOR: |
| | SBC 1007.4.2, THE WIDTH OF LANDINGS |
| | SHALL BE NOT LESS THAN THE WIDTH OFTHE |
| | STAIRWAYS THEY SERVE. EVERY LANDING |
| | SHALL HAVE A MINIMUM DIMENSION IN THE |
| | DIRECTION OF TRAVEL EQUAL TO THE WIDTH |
| | OF THE STAIRWAY. |
| | |
| | 3)- PENETRATIONS, SBC 705.6.1: THROUGH |
| | PENETRATIONS OF FIRE RATED HORIZONTAL AS |
| | SEMBLIES SHALL COMPLY WITH 705.6.1.1 OR |
| | 705.6.1.2. SHOW COMPLIANCE. |
| | |
| | 4)- SBC TABLE 803.3 INTERIOR MINIMUM |
| | FINISH CLASSIFICATION FOR WALLS &CEIL- |
| | ING. |
| | |
| | 5)- RESTROOMS: SBC 1204.2: PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH AN NONABSORB- |
| | ANT MATERIALFLOOR AND WALLS TO A HEIGTH |
| | OF 4'-0". |
| | |
| | 6)- SBC 104.2.2 ADDITIONAL INFORMATION |
| | REQUIRED, NEW CHASE PARTITION SHOW |
| | UL RATING OR GYPSUM ASSOC RATING. |
| | |
| | 7)- OFFICE 201/202 FL ACCESIBILITY CODE |
| | 4.13.6 MANEUVERING CLEARENCES AT DOORS, |
| | SHOW HOW YOU ARE GOING TO ACHIEVE CODE |
| | COMPLIANCE, SEE ATTACHMENT. THE SAME SIS |
| | TUATION HAPPENS FOR DOOR 5 INTO THE |
| | STAFF LOUNGE.OFFICE 208 & 301 REQUIRE |
| | THE 18" SIDE CLEARENCE PLAN INDICATES |
| | 17". |
| | |
| | 8)- AREA OF REFUGE SBC 1004.3.2.1 SHOW |
| | COMPLIANCE FOR 2ND & 3RD FLOOR. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X8412 |