| Plan Review Notes For Permit 01070575 |
| Permit Number |
01070575 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-16 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE PLANS AS TO EXHAUST AND | | | SUPPLY DUCTS FOR HOOD. | | | | | | PLANS NEED TO SHOW TERMINATION OF GREASE | | | DUCT. | | | | | | NOTE:GREASE DUCT SHALL HAVE A MINIMUM | | | SLOPE OF 1" PER FOOT TOWARD HOOD. | | | (1997 SMC 505.4) | | | | | | SEPERATE PERMIT AND PLANS REQUIRED FOR | | | FIRE SUPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|