Plan Review Notes
Plan Review Notes For Permit 01070575
Permit Number 01070575
Review Stop M
Sequence Number 1
Notes
Date Text
2001-07-16 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE PLANS AS TO EXHAUST AND
 SUPPLY DUCTS FOR HOOD.
  
 PLANS NEED TO SHOW TERMINATION OF GREASE
 DUCT.
  
 NOTE:GREASE DUCT SHALL HAVE A MINIMUM
 SLOPE OF 1" PER FOOT TOWARD HOOD.
 (1997 SMC 505.4)
  
 SEPERATE PERMIT AND PLANS REQUIRED FOR
 FIRE SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.