| Plan Review Notes For Permit 01070556 |
| Permit Number |
01070556 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-07-16 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PERMIT | | | APPLICATION WAS SUBMITTED FOR SERVICE | | | CHANGE, BUT A PLANWAS SUBMITTED SHOW- | | | -ING A HOUSE BEING WIRED? | | | PLEASE CLARIFY. | | | | | | 2)NOTE: PLEASE NOTE THAT IF HOUSE IS | | | BEING WIRED, MISSING SD`S AND COND UNIT | | | SHOWN FOR A/C. NFPA-72 2-2.1.1.1,440-11 | | | | | | 3)NOTE: PLEASE NOTE THAT SERVICE RISER | | | DIAGRAM SHOWS SERVICE BEING 3-PHASE?? | | | NO WIRE SIZES SHOWN. | | | | | | 4) PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | | AND PANEL(S). EQUIPMENT GROUNDING | | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | | | | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TOAND COLD WATER ALSO. | | | PER 250-50. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|