| Plan Review Notes For Permit 01070546 |
| Permit Number |
01070546 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-12-05 00:00:00 | ***************** UNSAT ************ | | | | | | 1)NOTE: PLEASE CLARIFY PLANS, POOL PANEL | | | IS SHOWN COMING FROM METER. IS THIS A | | | METER/MAIN COMBO, LIKE SHOWN ON PLANS? | | | | | | 2)NOTE: PLEASE SHOW LOCATION OF POOL | | | PANEL. PLEASE NOTE IF POOL PANEL HAS THE | | | SECOND MEANS OF DISC AND IS COMING | | | DIRECTLY FROM METER, THEN MAINS ARE | | | REQ`D TO BE GROUPED. 230-72 | | | | | | 3)NOTE:PLEASE CLARFI IF POOL PANEL IS | | | BEING FED FROM METER/MAIN? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|