Plan Review Notes
Plan Review Notes For Permit 01070541
Permit Number 01070541
Review Stop B
Sequence Number 5
Notes
Date Text
2002-02-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070541
 4301 S DIXIE HWY
 "PLAN REVIEW"
  
 SBC= 1997 STANDARD BUILDING CODE
  
 PLANS SHALL BE SUBMITTED FOR PERMIT APP-
 LICATION NO LATER THAN FEB. 28,2002
 TO BE CONTINUED TO BE REVIEWED UNDER THE
 1997 STANDARD BUILDING CODE. PLAN SUBMIT
 TED FOR PERMIT APPLICATION ON MARCH 1,
 2002 SHALL BE REVIEWED UNDER THE 2001
 FLORIDA CODE.
  
 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THE CITY SHALL REQUIRE (2 COPIES) OF ALL
 PRODUCT TESTING REPORTS, SBCCI OR DADE
 COUNTY SHALL BE EXCEPTED. A LIST OF
 REPORTS ARE STILL LACKING:
 A) EXTERIOR DOORS
 B) GARAGE OVERHEAD DOORS
 C) SLIDDING GLASS DOORS
 D) WINDOWS
 E) GLASS BLOCK
 F) STORM SHUTTERS WITH FASTENING
 SCHEDULE. SHEET A8.4/1 THIS DETAIL
 SHALL REQUIRE PRODUCT TESTING INDICATING
 THIS CONFIGURATION OR ENGINEERED SITE
 SPECIFIC ENGINEERING, SIGNED & SEALED
 CALCULATIONS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412