Plan Review Notes
Plan Review Notes For Permit 01070541
Permit Number 01070541
Review Stop P
Sequence Number 4
Notes
Date Text
2002-01-05 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS REVIEWS - SHTS A7.1 &
 A7.2 PLEASE SHOW CLEAR FLOOR SPACE FOR
 ALL HDCP FIXTURES. FACBC SEC 4.22.5
 2) FROM PREVIOUS REVIEWS - SHTS A7.1 &
 A7.2 RM #11 SHOW CLEAR FLOOR SPACE SEC
 4.24.5
 3) FROM PREVIOUS REVIEWS - SHTS A7.1 &
 A7.2 TOILET ROOM #124 SHOW CLEAR FLOOR
 SPACE, CURB DETAIL FOR SHOWER, SHOWER
 CONTROL DETAIL, W/C TO BE 18" OFF WALL,
 SHOWER SIZE. FACBC SEC 4.1.3(11) & SEC
 4.21
 4) FROM PREVIOUS REVIEWS - SHTS A7.1 &
 A7.2 DORM ROOMS #118 & #132 COMPLY WITH
 SEC 4.22 ACCESSIBLE TOILET ROOMS CLEAR
 FLOOR SPACE. SHOWER STALL DETAILS FOR
 CURBS, GRAB BARS, CONTROLS, SEAT AND
 GIVE SHOWER DEMENSIONS SEC 4.21
 5) FROM PREVIOUS REVIEWS - PAGE P4.2,
 WATER RISER DIAGRAM. HOT WATER ONLY TO
 DISHWASHER. HOT AND COLD SHOWN.
 6) PAGE P4.2 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS TO BE LOCATED NEAR
 SOURCE OF SHOCK NEAR FIXTURE NOT ON TOP
 OF DROP AS SHOWN.
 7) FROM PREVIOUS REVIEW - SHT P4.2 GAS
 PERMIT APPLICATION REQUIREMENTS HAVE NOT
 ALL BEEN ADDRESSED AS REQUESTED. PLEASE
 SEE ATTACHED SHEET AND SUBMIT ADDITIONAL
 INFORMATION REQUIRED.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE STANDARD GAS CODE SEC. 305.4(I).
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 8) SHT A7.1 & A7.2 RM #118 DETAIL #4 PER
 FACBC SEC 4.17.3(2) ACCESSIBLE WATER
 CLOSET SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377