| 2002-01-05 00:00:00 | DENIED |
| | REFERENCE: SPC-94-FACBC-97 |
| | |
| | 1) FROM PREVIOUS REVIEWS - SHTS A7.1 & |
| | A7.2 PLEASE SHOW CLEAR FLOOR SPACE FOR |
| | ALL HDCP FIXTURES. FACBC SEC 4.22.5 |
| | 2) FROM PREVIOUS REVIEWS - SHTS A7.1 & |
| | A7.2 RM #11 SHOW CLEAR FLOOR SPACE SEC |
| | 4.24.5 |
| | 3) FROM PREVIOUS REVIEWS - SHTS A7.1 & |
| | A7.2 TOILET ROOM #124 SHOW CLEAR FLOOR |
| | SPACE, CURB DETAIL FOR SHOWER, SHOWER |
| | CONTROL DETAIL, W/C TO BE 18" OFF WALL, |
| | SHOWER SIZE. FACBC SEC 4.1.3(11) & SEC |
| | 4.21 |
| | 4) FROM PREVIOUS REVIEWS - SHTS A7.1 & |
| | A7.2 DORM ROOMS #118 & #132 COMPLY WITH |
| | SEC 4.22 ACCESSIBLE TOILET ROOMS CLEAR |
| | FLOOR SPACE. SHOWER STALL DETAILS FOR |
| | CURBS, GRAB BARS, CONTROLS, SEAT AND |
| | GIVE SHOWER DEMENSIONS SEC 4.21 |
| | 5) FROM PREVIOUS REVIEWS - PAGE P4.2, |
| | WATER RISER DIAGRAM. HOT WATER ONLY TO |
| | DISHWASHER. HOT AND COLD SHOWN. |
| | 6) PAGE P4.2 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS TO BE LOCATED NEAR |
| | SOURCE OF SHOCK NEAR FIXTURE NOT ON TOP |
| | OF DROP AS SHOWN. |
| | 7) FROM PREVIOUS REVIEW - SHT P4.2 GAS |
| | PERMIT APPLICATION REQUIREMENTS HAVE NOT |
| | ALL BEEN ADDRESSED AS REQUESTED. PLEASE |
| | SEE ATTACHED SHEET AND SUBMIT ADDITIONAL |
| | INFORMATION REQUIRED. |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER STANDARD |
| | GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE STANDARD GAS CODE SEC. 305.4(I). |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER STANDARD GAS CODE SEC. 305.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | STANDARD GAS CODE SEC. 402. |
| | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 8) SHT A7.1 & A7.2 RM #118 DETAIL #4 PER |
| | FACBC SEC 4.17.3(2) ACCESSIBLE WATER |
| | CLOSET SHALL BE LOCATED IN THE CORNER, |
| | DIAGONAL TO THE DOOR. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |