Plan Review Notes
Plan Review Notes For Permit 01070541
Permit Number 01070541
Review Stop B
Sequence Number 4
Notes
Date Text
2002-01-07 00:00:00BUIDING PLAN REVIEW
 PERMIT # 01070541
 4301 S DIXIE
 "PLAN REVIEW"
  
 SBC= 1997 STANDARD BUILDING CODE
  
 ***** PLANS SUBMITTED FOR PLAN REVIEW
 JULY 2001 SHALL BE REVIEWED UNDER THE
 1997 BUILDING CODE. IF PLANS ARE NOT SUB
 MITTED FOR PERMIT BEFORE MARCH 1/2002,
 PLANS WILL THEN REVIEWED UNDER THE
 2002 FLORIDA CODE.
  
 1)104.2.2 A SURVEY LESS THAN A YEAR
 OLD.
  
 2)- SBC 1804.2.2 AMENDMENTS, SOILS
 REPORT WITH THE MINIMUM BEARING VALUE.
  
 3)- FL ENERGY CODE/ W MANUAL J
  
 4)- STRUCTURE IS LOCATED IN A FIRE
 DISTRICT, F-102.4 ROOF COVERINGS SHALL
 CONFORM TO THE REQUIREMENTS OF A CLASS
 A OR B ROOF COVERING, PROVIDE MANUFAC-TU
 RES SPEC.
  
 5)- SHEET S1.1 STRUCTURAL DESIGN
 CRITERIA, THE PLANS FILED UNDER THE
 1997 SBC ARE TO BE DESIGNED UNDER ASCE
 7/95. STRUCTURAL PLANS THAT ARE TO BE
 DESIGNED TO THE HIGHER WIND SPEED NEED
 TO INDICATE: ASCE 7/95 / ASCE 7/98.
 PLANS SUBMITTED FOR PERMIT APPLICATION
 AFTER MARCH 1/2002 SHALL BE DESIGNED TO
 ASCE 7-98.
  
 6)-SBC 1606.2.6.2 COMPONENTS & CLADDING
 THE CITY WILL REQUIRE (2 COPIES) OF
 PRODUCT TESTING REPORTS FOR THE FOLLOW-
 ING ITEMS:
 A) EXTERIOR DOORS
 B) GARAGE OVERHEAD DOORS
 C) SLIDDING GLASS DOORS
 D) WINDOWS
 E) GLASS BLOCK THIN, THICK WALL OR IF
 SOLID?
 F) SKYLIGHTS
 G) STORM SHUTTERS
 H) ROOF ASSEMBLIES /TILE
 ALL EXTERIOR WALL OPENINGS SHALL REQUIRE
 THE POSITIVE / NEGATIVEPRESSURES, IN-
 DICATE ON WALL ELEVATIONS. SEE CITY
 INTERPRETATION FOR LARGE MISSLE REISI-
 TANCE TESTING FOR GLAZED OPENINGS.
  
 SHEET A8.4/1 THIS DETAIL SHALL REQUIRE
 PRODUCT TESTING INDICATING THIS CONFIGU-
 RATION OR SITE SPECIFIC ENGINEERING.
  
 7) SHEET A8.3 DETAIL 10/11 INDICATE 1/2"
 EXPANSION BOLTS, NO SPACING OR MIN.
 EMBEDMENT.
  
 ***** PLANS FILED UNDER THE 2001
 FLORIDA CODE, FLORIDA STATE STATUTE
 553.80.2(B) THE LOCAL GOVERNMENT SHALL
 IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT
 CODE VIOLATION, A FEE OF FOUR TIMES THE
 AMOUNT OF THE PROPORTION OF THE PERMIT
 FEE ATTRIBUTED TO PLAN REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412