| 2001-10-26 00:00:00 | DENIED |
| | REFERENCES: SPC-94 - FACBC-97 - SGC-97 |
| | |
| | 1) FS 61G15-23.002(1) PLANS TO BE SIGNED |
| | DATED AND SEALED. 2 COPIES REQUIRED. |
| | 2) FS 61G1-16.003 PLANS TO BE SIGNED, |
| | DATED AND SEALED. 2 COPIES REQUIRED. |
| | 3) PAGES A7.1/A7.2 FROM PREVIOUS REVIEWS |
| | PLEASE SHOW CLEAR FLOOR SPACE FOR ALL |
| | HDCP FIXTURES. FACBC SEC 4.22.5 SHT P2.1 |
| | 4) FROM PREVIOUS PLAN REVIEWS. PAGES - |
| | A7.1/A7.2 RM #11, PANTRY (BREAK RM) SINK |
| | TO COMPLY WITH SEC 2.24.1 ACCESSIBLE, |
| | SEC 2.24.2 HEIGHT, CLEAR FLOOR SPACE SEC |
| | 2.24.5. |
| | 5) FROM PREVIOUS PLAN REVIEWS. PAGES - |
| | A7.1/A7.2 TOILET ROOM #124, PRIVATE |
| | TOILET RM TO BE ADAPTABLE. SHOW DETAILS |
| | FOR BACKING, CLEAR FLOOR SPACE, CURB, |
| | W/C TO BE 18" OFF WALL, SHOWER CONTROLS |
| | AND SHOWER SIZE. FACBC SEC 4.1.3(11) & |
| | SEC 4.21. |
| | 6) FROM PREVIOUS REVIEWS. PAGE A7.1/A7.2 |
| | DORM RMS #118 & #132 COMPLY WITH SEC |
| | 4.22, ACCESSIBLE TOILET RM'S CLEAR FLOOR |
| | SPACE. SHOW SHOWER STALL DETAILS FOR |
| | CURBS, GRAB BARS, CONTROLS, SEAT AND |
| | GIVE SHOWER DEMENSIONS. SEC 4.21 |
| | 7) PAGE P3.1 MED STORAGE RM #106, INDIR- |
| | ECT WASTE SHALL GO TO FLOOR SINK WITH |
| | TRAP PRIMER. STILL SHOWN GOING TO FLOOR |
| | DRAIN. FROM PREVIOUS REVIEW. |
| | 8) PAGE P4.2 WATER RISER DIAGRAM, HOT |
| | WATER ONLY TO DISHWASHER. |
| | 9) PAGE P4.1 SANT RISER DIAGRAM FLOOR |
| | DRAIN MISSING BY S/5 RM #124 |
| | 10) PAGE P3.1 THREE COMPARTMENT SINK IN |
| | KITCHEN SHALL HAVE INDIVIDUAL TRAPS TO |
| | EACH COMPARTMENT. SPC SEC 1001.8.1 |
| | 11) PAGE P3.1 PANTRY ROOM ENLARGEMENT |
| | SHOWS SINK P-19 BEHIND P-15 SINK, PAGE |
| | P4-1 SANITARY RISER DIAGRAM SHOWS A P-4 |
| | FOR THAT FIXTURE. PLEASE CLAIRFY. |
| | 12) GAS PERMIT APPLICATION REQUIREMENTS |
| | HAVE NOT BEEN ADDRESSED AS REQUESTED. |
| | PLEASE ADDRESS ALL REQUIREMENTS. |
| | 13) A MEETING AT CITY HALL SHOULD BE |
| | SCHEDULED TO ADDRESS ISSUES THAT NEED TO |
| | BE ADDRESSED FOR ALL TRADES AND BLDG. |
| | |