| Plan Review Notes For Permit 01070541 |
| Permit Number |
01070541 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-10-22 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. | | | SHOULD READ 1985 EDITION NOT 1997 | | | EDITION. | | | 2) OPENINGS BETWEEN THE MEDIAN ONLY | | | PROVIDES FOR 11 FEET IN CLEAR WIDTH. HOW | | | IS FIRE APPARATUS EXPECTED TO PASS | | | THROUGH THESE OPENINGS. | | | 3) THE FIRE HYDRANT PLANNED FOR USE | | | IS TO MEET UTILITY DEPARTMENT STANDARDS. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD,DUCT,AND EXTINGUISHING SYSTEMS. | | | 5) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA STANDARDS. | | | 6) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. | | | 7) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED WITH PLANS. | | | 8) ONLY TWO DOORS ARE SHOWN AS LABELED | | | DOORS. PLEASE CLARIFY. | | | 9) PLEASE SEE PREVIOUS PLAN REVIEW | | | COMMENTS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|