2001-10-22 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 1985 EDITION NOT 1997
 EDITION.
 2) OPENINGS BETWEEN THE MEDIAN ONLY
 PROVIDES FOR 11 FEET IN CLEAR WIDTH. HOW
 IS FIRE APPARATUS EXPECTED TO PASS
 THROUGH THESE OPENINGS.
 3) THE FIRE HYDRANT PLANNED FOR USE
 IS TO MEET UTILITY DEPARTMENT STANDARDS.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT,AND EXTINGUISHING SYSTEMS.
 5) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA STANDARDS.
 6) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
 7) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED WITH PLANS.
 8) ONLY TWO DOORS ARE SHOWN AS LABELED
 DOORS. PLEASE CLARIFY.
 9) PLEASE SEE PREVIOUS PLAN REVIEW
 COMMENTS.
  