2001-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070541
 4301 S DIXIE HWY
 PLAN CHECK # 01070541
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 ***** PLANS SUBMITTED FOR PLAN REVIEW
 UNDER 1997 SBC MUST APPLY FOR APPLICA-
 TION FOR PERMIT BEFORE DEC 31/2001.
 PLANS SUBMITTED FOR APPLICATION FOR
 PERMIT AFTER DEC. 31,2001 WILL BE REVIEW
 ED UNDER THE 2001 FLORIDA BUILDING CODE.
 ALL PRODUCT TESTING WILL ALSO HAVE TO RE
 FLECT THE HIGHER WIND REQUIREMENTS*****
  
 1)- STATE STATUTE 481 REQUIRES PLANS
 SUBMITTED FOR PUBLIC RECORD BE SIGNED
 SEALED & DATED BY THE DESIGN PROFESSION-
 AL.
  
 2)- SBC 104.2.2 A SURVEY LESS THAN A
 YEAR OLD.
  
 3)- SBC 1804.2.2* SOILS REPORT WITH THE
 MINIMUM BEARING VALUE.
  
 4)- FL ENERGY CODE ENRGY CALCULATIONS
 INCLUDING MANUAL J.
  
 5)- FIRE DISTRICT F-102.4 ROOF COVERINGS
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASSA OR B ROOF COVERINGS, PPROVIDE MAN
 UFACTURES SPECS.
  
 6)- S1.1 STRUCTURAL DESIGN CRITERIA,
 THE STATE REQUIRES THAT PLANS BE REVIEW-
 ED UNDER ASCE 7-95 WHICH IS GOVERENED BY
 THE 1997 STANDARD BUILDING CODE.THE
 ASCE7-98 WILL CONFORM TO THE 2001 FL
 CODE, MORE RESTRICTIVE CODE.IF THE
 DESIGN PRO. DESIRE TO BUILD TO THE MORE
 RESTRICTIVE CODE DESIGNATE IT BY
 " ASCE 7-95/ ASCE 7-98".
  
 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THE CITY WILL REQUIRE PRODUCT TESTING
 REPORTS (2 COPIES) FOR THE FOLLOWING
 ITEMS:
 A) EXTERIOR DOORS
 B) OVERHEAD GARAGE DOORS
 C) SLIDING GLASS DOORS
 D) WINDOWS
 E) GLASS BLOCK
 F) SKYLIGHTS
 G) STORM SHUTTERS
 H) ROOFING ASSEMBLIES/ TILE
  
 ALL WALL OPENINGS (DOORS & WINDOWS) WILL
 REQUIRE THE POSITIVE / NEGATIVE PRES-
 SURES THAT WILL BE APPLIED, IMPORTANCE
 FACTOR INTO THE OPENINGS. SEE THE CITY
 INTERPRETATION FOR LARGE MISSLE RESIS-
 TANCE TESTING FOR GLAZED OPENINGS.
  
 SHEET A8.4/1 THIS DETAIL WILL REQUIRE
 PRODUCT TESTING SHOWING THIS CONFIGURA-
 TION OR SITE SPECIFIC ENGINEERING.
  
 8)- SHEET A8.1 DETAIL 2 SBC 1204.2
 REQUIRES THE NONABSORBANT WALL MATERIAL
 BE 48" ABOVE FINISH FLOOR.
  
 9)- WINDOW BUCK DETAIL SHEET A8.4 DETAIL
 #2, 1/2" TAPCONS W/ 4" EMBEDMENT? MANUFA
 CTURES SPEC BOOKS INDICATE 3/16"
 AND 1/4" TAPCONS.
  
 10)- SHEET A8.3 DETAIL 10/11 INDICATE
 1/2" EXPANSION BOLTS NO SPACING OR MIN.
 EMBEDMENT?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412