Plan Review Notes
Plan Review Notes For Permit 01070541
Permit Number 01070541
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-09-17 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) PROVIDE MORE DETAILS ON OUTDOOR
 DIESEL FUEL TANK. ALSO PLEASE SHOW
 BOLLARD PROTECTION AND APPROPRIATE
 SIGNAGE FOR THE TANK.
 3) NO DOOR HARDWARE SHOWN ON DOOR
 SCHEDULE.
 4) SCALE ON LIFE SAFETY PLAN DOES NOT
 APPEAR TO BE CORRECT.
 5) WATER AND SEWER DETAILS DIFFICULT
 TO READ DUE TO SIZE OF WRITING.
 6) PLEASE PROVIDE DETAILS ON FIRE MAIN
 TYPE.
 7) A TWO-HOUR FIRE SEPARATION IS
 REQUIRED FOR THE GENERATOR ROOM IF IT
 WILL CONTAIN FLAMMABLE OR COMBUSTIBLE
 LIQUIDS. OPENING PROTECTIVES REQUIRED
 OF AT LEAST 1 1/2 HOURS.
 8) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS.
 9) KITCHEN EXHAUST TERMINATION SHALL
 BE A MINIMUM OF AT LEAST 10 FEET FROM
 SUPPLY AIR POINT.
 10) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 11) PLEASE PROVIDE MORE DETAILS ON GATE
 12) NO FIRE SEPARATION SHOWN BETWEEN
 BAY AND NORTH SIDE OF BUILDING?
 13) NO LIGHTING SHOWN FOR STAIR TOWER
 146.
 14) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. CUT SHEETS,
 WIRING DIAGRAMS AND BATTERY CALCULATIONS
 ARE REQUIRED. FIRE ALARM SYSTEM TO BE
 CLASS A OR FULLY ADDRESSABLE.
 15) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 1985 EDITION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910