| Date |
Text |
| 2001-09-17 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY |
| | CODE 3343-00. |
| | 2) PROVIDE MORE DETAILS ON OUTDOOR |
| | DIESEL FUEL TANK. ALSO PLEASE SHOW |
| | BOLLARD PROTECTION AND APPROPRIATE |
| | SIGNAGE FOR THE TANK. |
| | 3) NO DOOR HARDWARE SHOWN ON DOOR |
| | SCHEDULE. |
| | 4) SCALE ON LIFE SAFETY PLAN DOES NOT |
| | APPEAR TO BE CORRECT. |
| | 5) WATER AND SEWER DETAILS DIFFICULT |
| | TO READ DUE TO SIZE OF WRITING. |
| | 6) PLEASE PROVIDE DETAILS ON FIRE MAIN |
| | TYPE. |
| | 7) A TWO-HOUR FIRE SEPARATION IS |
| | REQUIRED FOR THE GENERATOR ROOM IF IT |
| | WILL CONTAIN FLAMMABLE OR COMBUSTIBLE |
| | LIQUIDS. OPENING PROTECTIVES REQUIRED |
| | OF AT LEAST 1 1/2 HOURS. |
| | 8) NO FIRE SPRINKLER OR HYDRAULIC |
| | CALCULATIONS PROVIDED WITH PLANS. |
| | 9) KITCHEN EXHAUST TERMINATION SHALL |
| | BE A MINIMUM OF AT LEAST 10 FEET FROM |
| | SUPPLY AIR POINT. |
| | 10) PLEASE PROVIDE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS. |
| | 11) PLEASE PROVIDE MORE DETAILS ON GATE |
| | 12) NO FIRE SEPARATION SHOWN BETWEEN |
| | BAY AND NORTH SIDE OF BUILDING? |
| | 13) NO LIGHTING SHOWN FOR STAIR TOWER |
| | 146. |
| | 14) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM. CUT SHEETS, |
| | WIRING DIAGRAMS AND BATTERY CALCULATIONS |
| | ARE REQUIRED. FIRE ALARM SYSTEM TO BE |
| | CLASS A OR FULLY ADDRESSABLE. |
| | 15) WRONG LIFE SAFETY CODE REFERENCED. |
| | SHOULD READ 1985 EDITION. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |